3-19
3.3.2 Control cable selection and wiring
Control cables should be connected to terminal block TM2, Choose power & Control
cables according to the following criteria
:
Use copper wires with correct diameter and temperature rating of 65/70°C
Minimum cable voltage rating for 200V type inverters should be 300VAC. Minimum cable
voltage rating for 400V type inverters should be 600VAC
Route all cables away from other high voltage or high current power lines to reduce
interference effects。
Use a twisted pair shielded cable and connect the shield (screen) wire to the ground
terminal at the inverter end only. Cable length should not exceed 50 meters