Appendix 1 Instructions for UL
AP
1
‐
3
UL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued
compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Main Circuit Terminal Wiring
UL approval requires crimp terminals when wiring the drive’s main circuit terminals. Use crimping tools as
specified by the crimp terminal manufacturer. Teco recommends crimp terminals made by NICHIFU for the
insulation cap. The table below matches drives models with crimp terminals and insulation caps. Orders can be
placed with a Teco representative or directly with the Teco sales department.
Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge mm2 (AWG)
Terminal Crimp Terminal
Tool
Insulation
11-201(series)
R/L1, S/L2, T/L3 U/T1, V/T2, W,T3
Screws
Model No.
Machine No.
Model No.
11-201-20-2P5-00
2 (14)
M3.5
R2-3.5
Nichifu NH 1/9
TIC 2
11-201-20-201-00
2 (14)
M3.5
R2-3.5
Nichifu NH 1/9
TIC 2
11-201-20-202-00
3.5 (12)
M4
R5.5-4
Nichifu NH 1/9
TIC 3.5
11-201-20-203-00
5.5 (10)
M4
R5.5-4
Nichifu NH 1/9
TIC 5.5
11-201-23-202-00
3.5 (12)
M4
R5.5-4
Nichifu NH 1/9
TIC 3.5
11-201-23-205-00
5.5 (10)
M4
R5.5-4
Nichifu NH 1/9
TIC 5.5
11-201-23-208-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-23-210-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-23-215-00
22 (4)
M6
R22-6
Nichifu NOP 60/150H
TIC 22
11-201-23-220-00
22 (4)
M6
R22-6
Nichifu NOP 60/150H
TIC 22
11-201-23-225-00
22 (4)
M6
R22-6
Nichifu NOP 60/150H
TIC 22
11-201-23-230-00
60 (1/0)
M8
R60-8
Nichifu NH 1/9
TIC 60
11-201-23-240-00
60 (1/0)
M8
R60-8
Nichifu NH 1/9
TIC 60
11-201-43-401-00
2 (14)
M3.5
R2-3.5
Nichifu NH 1/9
TIC 2
11-201-43-402-00
2 (14)
M3.5
R2-3.5
Nichifu NH 1/9
TIC 2
11-201-43-403-00
2 (14)
M4
R2-4
Nichifu NH 1/9
TIC 2
11-201-43-405-00
2 (14)
M4
R2-4
Nichifu NH 1/9
TIC 2
11-201-43-408-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-43-410-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-43-415-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-43-420-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-43-425-00
8 (8)
M4
R8-4
Nichifu NOP 60
TIC 8
11-201-43-430-00
14 (6)
M6
R14-6
Nichifu NOP 60/150H
TIC 14
11-201-43-440-00
38 (2)
M8
R38-8
Nichifu NOP 60/150H
TIC 38
11-201-43-450-00
38 (2)
M8
R38-8
Nichifu NOP 60/150H
TIC 38
11-201-43-460-00
38 (2)
M8
R38-8
Nichifu NOP 60/150H
TIC 38
11-201-43-475-00
38 (2)
M8
R38-8
Nichifu NOP 60/150H
TIC 38
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......