AP 3-5
Register and Data Format
Command Data (Read/Write)
Register No.
Bit
Content
2500H
Reserved
2501H
O
p e
r a
t i o
n S
i g
n a
l
0 Operation Command 1 : Run
0 : Stop
1 Reverse Command
1 : Reverse 0 : Forward
2 External Fault
1 : Fault
3 Fault Reset
1 : Reset
4 Reserved
5 Reserved
6 Multi-function Comm S1
1 :“ON”
7 Multi-function Comm S2
1 :“ON”
8 Multi-function Comm S3
1 :“ON”
9 Multi-function Comm S4
1 :“ON”
A Multi-function Comm S5
1 :“ON”
B Multi-function Comm S6
1 :“ON”
C Reserved
D Reserved
E Inverter mode
1 : “ON”
F
Reserved
2502H
*Frequency Command (Unit: 0.01Hz)
2503H
Reserved
2504H
Reserved
2505H
AO1 (0.00V ~ 10.00V)
2506H
Reserved
2507H
Reserved
2508H
Reserved
2509H
Reserved
250AH
Reserved
250BH
Reserved
250CH
Reserved
250DH
Reserved
250EH
Reserved
250FH
Static Auto Tune 1:”ON”
2510H
G12-00 H-WORD
2511H
G12-00 L-WORD
Note : Write in zero for Not used BIT, do not write in data for the reserved register.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......