AP 3-10
Loop back test [08H]
Check the communication between the master and the follower (inverter). The data used can
be arbitrary.
ASCII Mode
Command Message Response Message (Normal) Response Message (Error)
3AH
STX
3AH
STX
3AH
STX
30H
Node
Address
30H
Node
Address
30H
Node
Address
31H
31H
31H
30H
Function
30H
Function
38H
Function
38H
38H
38H
30H
Test Code
30H
Test Code
30H
Exception
code
30H
30H
33H
30H
30H
30H
LRC CHECK
30H
30H
36H
41H
DATA
41H
DATA
0DH
END
0AH
35H
35H
33H
33H
37H
37H
31H
LRC CHECK
31H
LRC CHECK
42H
42H
0DH
END
0DH
END
0AH
0AH
RTU Mode
Command Message Response Message (Normal) Response Message (Error)
Node Address
01 H
Node Address
01H
Node Address
01H
Function
08H
Function
08H
Function
88H
Test Code
High 00H
Test Code
High
00H
Exception code
03H
Low 00H
Low
00H
CRC-16
High
06H
Number of
Registers
High A5H
Number of
Registers
High
A5H
Low
01H
Low 37H
Low
37H
CRC-16
High DAH
CRC-16
High
DAH
Low 8DH
Low
8DH
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......