AP 3-26
No.
Object Name
Description
Unit
Classification
Range
AI8
Motor R-HP
Motor rated power
horsepower
R
AI9
Motor R-RPM
Motor rated rotation speed
No Units
R
AI10
Motor R-Hz
Motor rated frequency
Hz
R
AI11
CarrierFreq
Carrier frequency
KiloHertz
R
4-16
AI12
Comm Station
INV communication station
No Units
R
1-254
AI13
BaudRate
Baudrate setting
No Units
R
0-3
AI14
BacnetSel
Communication mode selection
No Units
R
0-1
AI15
DevInstance
Inverter number
No Units
R
1-254
Table 4 Analog output property list (Read/Write)
No.
Object Name
Description
Unit
Classification
Range
AO0
Set frequency
Frequency command
Hz
R/W
0-599
AO1
TB2 AO1
Analog output voltage 1
Volt
R
0-10
AO2
-
-
-
-
-
AO3
Motor R-Amp
Motor rated current
Amps
R/W
0-65535
AO4
PwrL Sel
Momentary stop and restart selection
No Units
R
0-1
AO5
RestartSel
Number of Fault Auto-Restart Attempts
No Units
R
0-10
AO6
RestartDelay
Fault Auto-Restart Time
seconds
R
0-7200
AO7
FreqCommand1
Speed frequency setting-stage 0
Hz
R/W
0-599
AO8
FreqCommand2
Speed frequency setting-stage 1
Hz
R/W
0-599
AO9
FreqCommand3
Speed frequency setting-stage 2
Hz
R/W
0-599
AO10
FreqCommand4
Speed frequency setting-stage 3
Hz
R/W
0-599
AO11
FreqCommand5
Speed frequency setting-stage 4
Hz
R/W
0-599
AO12
FreqCommand6
Speed frequency setting-stage 5
Hz
R/W
0-599
AO13
FreqCommand7
Speed frequency setting-stage 6
Hz
R/W
0-599
AO14
FreqCommand8
Speed frequency setting-stage 7
Hz
R/W
0-599
AO15
FreqCommand9
Speed frequency setting-stage 8
Hz
R/W
0-599
AO16
FreqCommand10
Speed frequency setting-stage 9
Hz
R/W
0-599
AO17
FreqCommand11
Speed frequency setting-stage 10
Hz
R/W
0-599
AO18
FreqCommand12
Speed frequency setting-stage 11
Hz
R/W
0-599
AO19
FreqCommand13
Speed frequency setting-stage 12
Hz
R/W
0-599
AO20
FreqCommand14
Speed frequency setting-stage 13
Hz
R/W
0-599
AO21
FreqCommand15
Speed frequency setting-stage 14
Hz
R/W
0-599
AO22
FreqCommand16
Speed frequency setting-stage 15
Hz
R/W
0-599
AO23
RunMode
Main run command source
No Units
R/W
0-2
AO24
ReverseOper
Direction locked command
No Units
R/W
0-1
AO25
StoppingSel
Stop modes selection
No Units
R/W
0-1
AO26
FrequenceComm
Main frequency command source
No Units
R/W
0-5
AO27
FreqUpperLim
Upper limit frequency
Hz
R/W
0-599
AO28
FreqLowerLim
Lower limit frequency
Hz
R/W
0-598.99
AO29
Acc Time1
Acceleration time 1
seconds
R/W
0-6000.0
AO30
Dec Time1
Deceleration time 1
seconds
R/W
0-6000.0
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......