7.
Safety Input logic & Status
TECO 11-301 safety stop function prevents a drive from supplying rotational energy to motors.
Dual safety channels “S1” and “S2” cut off the gate-drive power for IGBT to turn off.
Diagram below shows the basic block diagram design of the safety and interface
for the safety inputs.
Figure 1 11-301 safety stop function diagram
WARNING
The safety stop function does not isolate electrically between drive and motor. To avoid
an electric shock hazard, disconnect/isolate power to the drive and verify to ensure that
the voltage is zero before performing any work on the motor (refer to your drive’s
User
Manual
for discharging time).
Directives
TECO 11-301 safety stop function meets the following directives and categories:
ISO13849-1:2008 Category 3/PLd
IEC62061:2005
IEC61800-5-2:2007
IEC61508 SIL2
IEC60204-1:2006 Stop category 0
External
Safety
Device
Approved
to SIL2 / Pld
Summary of Contents for E510-201-SH