3-30
6.
If control mode (00-00) is set to 2 (SLV mode) and maximum frequency (01-02) is larger than
80Hz, the carrier frequency range is 2~8kHz.
The following table shows maximum output frequency for each control mode.
Duty Cycle Control Mode
Other Setings
Max. Output Frequency
Heavy Duty
(00-27=0)
V/F
Maximum output frequency is 599Hz
599Hz
SLV
200V 1~10HP, 400V 1~15HP
150Hz
200V 15~20HP, 400V 20HP
110Hz
400V 25HP
100Hz
200V 25~40HP, 400V 30~75HP,
carrier (11-01) is set as 8K or below 8K
100Hz
200V 25~40HP, 400V 30~75HP,
carrier (11-01) is above 8K
80Hz
PMSLV
Please refer parameter group 22 of
chapter 4.3 (PM motor parameter group)
599Hz
Normal
Duty
(00-27=1)
V/F
200V 25~40HP, 400V 30~75HP
The maximum frequency is 120Hz
120Hz
SLV /PMSLV
Without standard loading mode
-
Model
No.
Input Voltage
(V)
Input
Current
(A)
Max. Output
Voltage (V)
Rated Output
Current (A)
Output
Power
(KW)
11-301-21-xxx-30 series
11-301-21-2P5-30
200-240 / 1
Ф
8.5
240/3
Ф
3.1
0.4
11-301-21-201-30
200-240 / 1
Ф
12
240/3
Ф
4.5
0.75
11-301-21-202-30
200-240 / 1
Ф
16
240/3
Ф
7.5
1.5
11-301-21-203-30
200-240 / 1
Ф
23.9
240/3
Ф
10.5
2.2
11-301-43-xxx-30 series
11-301-43-401-30
380-480 / 3
Ф
4.2
480/3
Ф
2.3
0.75
11-301-43-402-30
380-480 / 3
Ф
5.6
480/3
Ф
3.8
1.5
11-301-43-403-30
380-480 / 3
Ф
7.3
480/3
Ф
5.2
2.2
11-301-43-405-30
380-480 / 3
Ф
11.6
480/3
Ф
9.2
4.0
11-301-43-408-30
380-480 / 3
Ф
17.0
480/3
Ф
13.0
5.5
11-301-43-410-30
380-480 / 3
Ф
23.0
480/3
Ф
17.5
7.5
11-301-43-415-30
380-480 / 3
Ф
31.0
480/3
Ф
24
11
11-301-43-420-30
380-480 / 3
Ф
38.0
480/3
Ф
32
15
11-301-43-425-30
380-480 / 3
Ф
48.0
480/3
Ф
40
18.5
11-301-43-430-30
380-480 / 3
Ф
48.9/63.0
480/3
Ф
45/58
22/30
11-301-43-440-30
380-480 / 3
Ф
65.2/78.3
480/3
Ф
60/73
30/37
11-301-43-450-30
380-480 / 3
Ф
81.5/95.7
480/3
Ф
75/88
37/45
11-301-43-460-30
380-480 / 3
Ф
98.9/112
480/3
Ф
91/103
45/55
11-301-43-475-30
380-480 / 3
Ф
130/159
480/3
Ф
118/145
55/75
For 11-301-43-430/40/50/60/75-30, these models have two operation modes for setting.
N.D:Normal Duty operation mode.
H.D:Heavy Duty operation mode.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......