3-31
3.4.2 General specifications
Item
E510s
Control mode
V/F, SLV, PMSLV control mode
Frequency
Output Frequency
0.01~599.00Hz
Starting Torque
150% / 1Hz (SLV mode),150% / 3Hz(V/F mode)
Frequency resolution
Digital input:0.01Hz
Analog input:0.06Hz/60Hz
Frequency setting
Keypad:set directly with ▲▼keys or the VR on the keypad
External input terminals: AI1、AI2 (0/2-10V, 0/4-20mA)
Multifunction input UP/DOWN function(Group 3)
Set frequency by communication method
Frequency limit
Lower and upper frequency limits 3 skip frequency settings.
Run Operation set
Keypad RUN/STOP buttom
External terminals:
Multi-operation mode 2/3 wires selection
JOG operation
Run signal by communication method
Main
Control
Features
V / F curve setting
15 fixed curves and 1 customized curve
Carrier frequency
1~16kHz (factory setting is 5kHz)
Acceleration and
deceleration control
2 off acceleration/deceleration time parameters
4 off S curves parameters
Multifunction input
Refer to description on Group 3
Multifunction output
Refer to description on Group 3
Multifunction analog output
Refer to description on Group 4
Main features
Overload detection, 16 preset speed, Auto-run, Acc/Dec
switch(2 stages), Main/Alt run command select, Main/Alt
frequency command select, PID control, Torque boost, V/F
start frequency, Fault reset, Fire mode,
Multi-Pump function.
Display
LED display
Parameter, Paramete value, Frequency, Line speed, DC
voltage, Output voltage, Output current, PID feedback, Input
and output terminal status, Heat sink temperature, Firmware
version, Fault list.
LED status indicator
Run, Stop, Forward, Reverse and etc.
Protective
Functions
Overload protection (OL1)
Electrical overload protection curve
Overload protection (OL2)
H.D mode:150% for 60s
(200% for 2s)
N.D mode:120% for 60s
Over voltage
200V Class:DC bus voltage higher than 410Vdc
400V Class:DC bus voltage higher than 820Vdc
Under Voltage
200V Class:DC bus voltage lower than 190V
400V Class:DC bus voltage lower than 380V
Momentary Power Loss
Restart
Inverter auto-restart after a momentary power loss
Stall Prevention
Stall prevention for acceleration/deceleration operation
Short-circuit output terminal
Electronic circuit protection
Grounding Fault
Electronic circuit protection
Other protection features
Protection for overheating of heat sink, Fault output, Reverse
prohibit, Prohibit for direct start after power up and error
recovery, Parameter lock up, STO (Safety Torque Off).
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......