3-36
3.4.4 Capacitor Reforming Guide After Long Storage
For correct performance of this product after long storage before use it is important that Inverter
Capacitors are reformed according to the guide below:
Storage
time
Procedure to re-apply voltage
≦1year
Apply rated voltage of inverter in the normal way
Between
1-2 years
Apply rated voltage of inverter(Note1) to the product for one hour before using the
inverter
≧2 years
Use a variable AC power supply to
1.
Connecting 25% rated voltage of inverter for 30 minutes.
2.
Connecting 50% rated voltage of inverter for 30 minutes.
3.
Connecting 75% rated voltage of inverter for 30 minutes.
4.
Connecting 100% rated voltage of inverter for 210 minutes.
Once the procedures completed, inverter just can be used normally
Note1:Please refer the rated voltage according to model label of inverter
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......