1-1
Chapter 1 Safety Precautions
1.1
Before Power Up
Danger
Make sure the main circuit connections are correct Single phase L1(L),L3(N), Three
phase L1(L),L2,L3(N) are power-input terminals and must not be mistaken for
T1,T2 and T3. Otherwise, inverter damage can result.
Caution
The line voltage applied must comply with the inverter’s specified input
voltage.(See the nameplate)
To avoid the front cover from disengaging, or other damge do not carry the
inverter by its covers. Support the drive by the heat sink when transporting.
Improper handling can damage the inverter or injure personnel and should be
avoided.
To avoid the risk of fire, do not install the inverter on a flammable object.Install on
nonflammable objects such as metal
This product provides the 10V/24V for internal use only, do not use as the power
supply sources for other external components, such as sensors, electronic
components ... etc., otherwise it will cause adverse situation.
When disconnecting the remote keypad, turn the power off first to avoid any
damage to the keypad or the inverter.
Caution
This product is sold subject to EN 61800-3 and EN 61800-5-1. In a domestic
environment this product may cause radio interference in which case the user
may be required to apply corrective measures.
This product offers motor over temperature protection function.
Caution
Work on the device/system by unqualified personnel or failure to comply with
warnings can result in severe personal injury or serious damage to material. Only
suitably qualified personnel trained in the setup, installation, commissioning and
operation of the product should carry out work on the device/system.
Only permanently-wired input power connections are allowed.
1.2
During Power Up
D
anger
Always turn OFF the power supply before attempting inverter installation and
wiring of the user terminals.
Wiring must be performed by a qualified personnel / certified electrician.
Make sure the inverter is properly grounded. (200V Class: Grounding impedance
shall be less than 100
Ω
. 400V Class: Grounding impedance shall be less than 10
Ω
.)
Please connect to the earth according to EN61800-5-1 standard request, For
system 430, 440, 450, 460 and 470, wiring size must be at least 10mm
2
(8 AWG)
only can comply the standard of leakage current.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......