Group 03 External Digital Input and Output Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
03-00
Multifunction Input
Terminal S1
0:Forward/Stop Command
0
-
O
O
O
1:Reverse/Stop Command
O
O
O
2:Multi-Speed/Position Setting Command 0
O
O
O
3:Multi-Speed/Position Setting Command 1
O
O
O
4:Multi-Speed/Position Setting Command 2
O
O
O
5:Multi-Speed/Position Setting Command 3
O
O
O
6:Forward Jog Run Command
O
O
O
03-01
Multifunction Input
Terminal S2
7:Reverse Jog Run Command
1
-
O
O
O
8:UP Frequency Increasing Command
O
O
O
9:DOWN Frequency Decreasing Command
O
O
O
10:Acceleration/ Deceleration Time Selection 2
O
O
O
11:Inhibit Acceleration/ Deceleration Command
O
O
O
12:Main/ Alternative Run Switch Function
O
O
O
13:Main/ Alternative Frequency Switch Function
O
O
O
03-02
Multifunction Input
Terminal S3
14:Emergency Stop (decelerate to zero and stop)
2
-
O
O
O
15:External Baseblock Command
(rotation freely to stop)
O
O
O
16:PID Control Disable
O
O
O
17:Fault Reset
O
O
O
18:Auto Run Mode Enable
O
O
O
19:Speed Search 1
O
O
X
20:Energy Saving (V/F only)
O
X
X
03-03
Multifunction Input
Terminal S5
21:Reset PID integral value to Zero
3
-
O
O
O
22:Counter Input
O
O
O
23:Counter reset
O
O
O
24:PLC Input
O
O
O
25:Pulse-In width measure(S3)
O
O
O
26:Pulse-In frequency measure(S3)
O
O
O
03-04
Multifunction Input
Terminal S5
27:Local/Romote selection
4
-
O
O
O
28:Remote mode selection
-
O
O
O
29:Jog Frequency Selection
O
O
O
33:DC Braking
-
O
O
O
03-05
Multifunction Input
Terminal S6
34:Speed Search 2
17
-
O
O
X
40:Switching between Motor 1/Motor 2
-
O
O
X
47:Fire mode
O
O
O
48:KEB Acceleration
O
X
X
57:Forced Frequency Run
O
O
O
63:Switch to Constant Pressure 2
O
O
O
65:Short-circuit braking
66:PID Control Disable 2
68:External Fault
69:External Overload
-
X
X
O
O
O
O
O
O
O
O
O
O
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......