4-22
Group 03 External Digital Input and Output Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
03-06
Up/Down frequency
step
0.00~5.00
O
O
O
03-07
Up/Down Keep
Frequency Status after
Stop Command
0:When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down
function is disabled
1:When Up/Down is used, the preset frequency
is reset to 0 Hz as the inverter stops.
2:When Up/Down is used, the preset frequency
is held as the inverter stops, and the UP/Down
is available.
3:When acceleration is used, the output
frequency will be updated.
0
-
O
O
O
03-08 S1~S6 DI scan Time 1~200
1
ms
O
O
O
03-09
Multi-Function
Terminal S1~ S4 type
selection
xxx0b:S1 A Contact, xxx1b:S1 B Contact
xx0xb:S2 A Contact, xx1xb:S2 B Contact
x0xxb:S3 A Contact, x1xxb:S3 B Contact
0xxxb:S4 A Contact, 1xxxb:S4 B Contact
0000b
-
O
O
O
03-10
Multi-Function
Terminal S5~ S6 type
selection
xxx0b:S5A Contact, xxx1b:S5 B Contact
xx0xb:S6 A Contact, xx1xb:S6 B Contact
0000b
-
O
O
O
03-11
Relay (R1A-R1C)
Output
0:During Running
1
-
-
O
O
O
1:Fault Contact Output
O
O
O
2:Frequency Agree
O
O
O
3:Setting Frequency Agree (03-13±03-14)
O
O
O
4:Frequency Detection 1 (≧03-13+03-14)
O
O
O
5:Frequency Detection 2 (≦ 03-13+03-14)
O
O
O
6:Automatic Restart
O
O
O
7:Momentary AC Power Loss
O
O
O
8:Rapid Stop
O
O
O
9:Base Block
O
O
O
10:Motor Overload Protection (OL1)
O
O
O
11:Drive Overload Protection (OL2)
O
O
O
12:Over-torque Threshold Level (OL3)
O
O
O
13:Preset Output Current Reached
O
O
O
14:Brake Control
O
O
O
15:PID Feedback Signal Loss
O
O
O
16:Single pre-set count (3-22~23)
O
O
O
17:Dual pre-set count (3-22~23)
O
O
O
18:PLC Status Indicator (00-02)
O
O
O
19:PLC control *
O
O
O
20:Zero Speed
O
O
O
30:Motor 2 Selection
O
X
X
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...