4-30
Group 07 Start/Stop Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
SLV
PM
SLV
07-00
Momentary Power Loss and
Restart
0:Disable
1:Enable
0
-
O
O
X
07-01 Fault Reset Time
0~7200
0
s
O
O
O
07-02
Number of Auto Restart
Attempts
0~10
0
-
O
O
O
07-03 Reset Mode Setting
0:Enable Reset Only when Run
Command is Off
1:Enable Reset when Run
Command is On or Off
0
-
O
O
O
07-04
Momentary Power Loss and
Restart
0:Enable Direct run on power up
1:Disable Direct run on power up
1
-
O
O
O
07-05 Delay-ON Timer
1.0~300.0
1.0
s
O
O
O
07-06
DC Injection Braking Start
Frequency
0.0~10.0
1.5
Hz
O
O
O
07-07
DC Injection Braking Level
(Current Mode)
0~100
50
%
O
O
O
07-08 DC Injection Braking Time
0.00~100.00
0.50
s
O
O
O
07-09 Stop Mode Selection
0:Deceleration to Stop
1:Coast to Stop
2:DC Braking Stop in All Fields
3:Coast to Stop with Timer
0
-
O
O
X
07-10 Speed Search Mode Selection
0:Normal Start
1:Execute Speed Search Once
2:Speed Search Start
0
-
O
O
O
07-13 Low Voltage Detection Level
200V:100~300
190
V
O
O
O
400V:250~600
380
07-15 DC Injection Brake Mode
0:
Current
Mode
1:
Voltage
Mode
1
O
O
O
07-16
DC Injection Braking Time at
Start
0.00~100.00
0.00
s
O
O
O
07-18 Minimum Base block Time
0.1~5.0
KVA
s
O
O
O
07-19
Speed Direction Search
Operation Current
0~100
50
%
O
O
X
07-20 Speed Search Operating Current 0~100
20
%
O
O
X
07-21
Integral Time of Speed
Searching
0.1~10.0
2.0
s
O
O
X
07-22 Delay Time of Speed Searching 0.0~20.0
0.2
s
O
O
X
07-23 Voltage Recovery Time
0.1~5.0
2.0
s
O
O
X
07-24
Direction-Detection Speed
Search Selection
0:Invalid
1
-
O
O
X
1:Valid
07-25 Low Voltage Detection Time
0.00~1.00
0.02
s
O
O
O
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......