4-31
Group 07 Start/Stop Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
SLV
PM
SLV
07-26
Start-up Mode Selection of SLV
Coast to Stop
0:Start With Speed Search
1:Normal Start
0
-
X
O
X
07-27
Start Selection after Fault During
SLV Mode
0:Start With Speed Search
1:Normal Start
0
-
X
O
X
07-28 Start after External BaseBlock
0:Start With Speed Search
1:Normal Start
0
-
O
O
X
07-29
Run Command Selection at the
Action of DC Braking
0:Not Allowable to Run
1:Allowable to Run
0
-
O
X
X
07-33
Start Frequency of Speed Search
Selection
0:Maximum Output Frequency
1:Frequency Command
0
-
O
O
X
07-34 Start Short-Circuit Braking Time 0.00~100.00
0.00
s
X
X
O
07-35 Stop Short-Circuit Braking Time 0.00~100.00
0.50
s
X
X
O
07-36
Short-Circuit Braking Current
Limited
0.0~200.0
100.0
%
X
X
O
07-37 Pre-Excitation Time
0.00~10.00
2.00
s
X
O
X
07-38 Pre-Excitation Level
50~200
100
%
X
O
X
07-39
Short-Circuit Braking Time of
PM Motor Speed Search
Function
0.00~100.00
0.00
s
X
X
O
07-40
DC Injection Braking Time of PM
Motor Speed Search Function
0.00~100.00
0.00
s
X
X
O
07-45 STP2 function selection
0:STP2 is enabled
1:STP2 is disabled
0
O
O
O
* :
If the maximum output frequency of motor is over 300HZ, the frequency resolution is changed to 0.1Hz
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......