4-33
Group 08 Protection Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
SLV
PM
SLV
08-14
Selection of
Over-Torque Action
0:Deceleration to Stop when Over Torque is
Detected.
1:Display Warning when Over Torque is
Detected. Go on Operation.
2:Coast to Stop when Over Torque is Detected
0
-
O
O
O
08-15
Level of Over-Torque
Detection
0~300
160
%
O
O
O
08-16
Time of Over-Torque
Detection
0.0~10.0
0.1
s
O
O
O
08-21
Limit of Stall Prevention
During Acceleration
1~100
50
%
O
O
O
08-22
Stall Prevention
Detection Time During
Run
2~100
100
ms
O
O
O
08-23
Ground Fault (GF)
Selection
0:Disable
1:Enbale
0
-
O
O
O
08-24
Operation Selection of
External Fault
0:Deceleration to Stop
1:Coast to Stop
2:Continuous Operation
0
-
O
O
O
08-25
Detection Selection of
External Fault
0:Immediately Detect When the Power is
Supplied
1:Start to Detect during Operation
0
-
O
O
O
08-35
Motor Overheating
Fault Selection
0:Disable
1:Deceleration to Stop
2:Coast to Stop
3:Keep Running
0
-
O
O
O
08-36
PTC Input Filter Time
Constant
0.00 ~ 5.00
2.00
s
O
O
O
08-38 Delay Time of Fan Off 0~600
60
s
O
O
O
08-39
Delay Time of Motor
Overheat Protection
1~300
60
s
O
O
O
08-40
Motor2 Acceleration
Stall Prevention Level
20~200
HD: 150
%
O
O
X
ND: 120
08-41
Motor2 Acceleration
Stall Prevention Limit
1~100
50
%
O
O
X
08-42 PTC Protection Level
0.1~10.0V
0.7
V
O
O
O
08-43 PTC Restart Level
0.1~10.0V
0.3
V
O
O
O
08-44 PTC Warning Level
0.1~10.0V
0.5
V
O
O
O
08-46
Temperature Agree
Level
0~254°C
0
°C
O
O
O
08-47
Temperature Reset
Level
0~254°C
0
°C
O
O
O
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......