Main Circuit Low Voltage Detection
Range
220V Class
【
150.0~210.0
】
440V Class
【
300.0~420.0
】
07-14
Kinetic Energy Back-up Deceleration Time
(
KEB
)
Range
【
0.0
】
: Disable
【
0.1
~
25.0
】
: KEB Deceleration Time
¾
07-14
= 0 KEB function disable
¾
07-14
≠
0 KEB function enable
Example: 220V system
Power Off
Power On
External power on Signal when
03-00~03-05=27
TM2
S1~S6
DC=190V
PN DC
Voltage
Frequency
Oouput
When 07-14?0
,
PN
Voltage below 190V KEB
function work
T?0
Deceleration
Time set by
07-14
※
Note:
1. When
07-14
≠
0, the momentary power loss and restart is disabled, the inverter will do KEB function.
2. When input power is turned off, CPU detects the DC bus Voltage and as soon as DC bus Voltage
becomes lower than190V (220V system) or 380V (440V system), then the KEB function is activated.
3. When KEB function is enabled, the inverter decelerate to zero by
07-14
, and the inverter stop
4. IF the power on signal enabled during the KEB function, the inverter accelerate to original frequency.