4-70
OV (over voltage), to avoid over voltage due to regeneration the output frequency will be increased..
Regeneration avoid ance can be set according to the selections above.
Example: Regeneration avoidance during acceleration.
In Regeneration avoidance operation
Vpn(DCV)
Set value of 11-14
outputfre
quency
Hz
t
t
Example: Regeneration avoidance during constant speed.
Set value of 11-14
t
t
In Regeneration avoidance operation
Vpn(DCV)
outputfre
quency
(
Hz
)
Example: Regeneration avoidance during deceleration.
t
t
Vpn(DCV)
outputfre
quency
(
Hz
)
Set value of 11-14
In Regeneration avoidance operation
11- 14
Regeneration Avoidance Operation Level
Range
【
300~800V
】
¾
Regeneration avoidance voltage detection level, if the bus voltage level is set too low, then
over-voltage protection will not be reached, but the actual deceleration time will be extended.
11- 15
Regeneration Avoidance Frequency Limit
Range
【
0.00
~
15.00Hz
】