4-72
¾
12- 04
≠
0
,
line speed is displayed while the inverter is running or stopped.
12- 05
Inputs and output Logic status display (S1 to S6) & RY1~2
Range
Read only(Panel read only)
¾
When any of S1 ~ S6 is turned on, corresponding segments on the digital display digits will be on.
¾
When relay output RY1/RY2 are on, the corresponding digit will be on as shown below.
Example 1: The following figure shows 12 - 05 display status,
when S1, S3, S5,S6 Inputs are ON and S2, S4, RY1 and RY2 are OFF.
S1 S2 S3 S4 S5 S6
Example 2: The following figure shows 12 - 05 display status
when S2, S3, S4 inputs are ON and S1, S5,S 6 are OFF but RY1and RY2 are ON.
RY1
RY2
12- 06
Alarm Selections for Inverter Components Life Expectancy
xxxx0:
life alarm of inrush current suppression circuit is invalid
xxxx1:
life alarm of inrush current suppression circuit is valid
xxx0x:
life alarm of control circuit capacitors is invalid
xxx1x:
life alarm of control circuit capacitors is valid
Range
xx0xx:
life alarm of main circuit capacitors is invalid
xx1xx:
life alarm of main circuit capacitors is valid
Example:set 12- 06=00111,if inrush current suppression circuit or control circuit capacitors or main circuit
capacitors is damaged,display LIFE1,LIFE2,LIFE3 respectively
. Alerts the user that inverter needs repair
12- 08
Display of inrush current suppression circuit
Range 0~100
¾
Display of Inrush current suppression circuit life expectancy level
12- 09
Display of control circuit capacitors
Range 0~100
¾
Display of control circuit capacitors life expectancy level
12- 10
Display of main circuit capacitors
Range 0~100
¾
Display of main circuit capacitors life expectancy level
12- 11
Output current when Fault appeared
Range ----
12- 12
Output voltage when fault appeared
Range ----
12- 13
Output frequency when fault appeared
Range ----
12- 14
DC bus voltage when fault appeared
Range ----
12- 15
Frequency command when fault appeared
Range ----
¾
In addition to the main circuit capacitors above, the theoretical value of life diagnosis are only for
reference.
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......