3.3.5 Considerations for peripheral equipment
(
Power
Ensure that the supply voltage is correct.
A molded-case circuit breaker or fused disconnect
must be installed between the AC source and the
inverter
Circuit
Breaker
& RCD
Use a molded-case circuit breaker that conforms
to the rated voltage and current of the inverter.
Do not use the circuit breaker as the run/stop
switch for the inverter.
Residual Current Circuit Breaker(RCD)
Current setting should be 200mA or above and the
operating time at 0.1 second or longer to prevent
malfunctions.
Magnetic
contactor
Normally a magnetic contactor is not needed.
A contactor can be used to perform functions such
as external control and auto restart after power
failure.
Do not use the magnetic contactor as the run/stop
switch of the inverter.
AC reactor for
power quality
improvement
When a 200V/400V inverter with rating below
15KW is connected to a high capacity power
source (600KVA or above) then an AC reactor can
be connected for power factor improvement and
reducing harmonics.
Input noise
filter
E510 inverter has a built-in filter to Class “A” first
Environment. (CategoryC2)
To satisfy the required EMC regulations for your
specific application you may require an additional
EMC filter.
Inverter
Connect the single phase power to Terminals,
L1(L) & L3(N).
Warning! Connecting the input terminals T1, T2,
and T3 to AC input power will damage the inverter.
Output terminals T1, T2, and T3 are connected to
U, V, and W terminals of the motor.
To reverse the motor rotation direction just swap
any two wires at terminals T1, T2, and T3.
Ground the Inverter and motor correctly.
Ground Resistance for 200V power<100 Ohms.
Ground Resistance for 400V power<10 Ohms
Motor
Three-phase induction motor. Voltage drop on motor
due to long cable can be calculated.
Volts drop should be < 10%.
Phase-to-phase voltage drop (V) =
3 ×resistance of wire (
Ω
/km)×length of
line(m)×current×
10
-3
Grounding
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......