3-31
3.4.2
General Specifications
Item
E510
Control Mode
V/F Control, Vector Control
Output Frequency
0.01~650.00Hz
Starting Torque
150%/1Hz(Vector)
Speed Control Range
1:50
Digital input
: 0.01Hz
Setting resolution
Analog input
:0.06Hz/60Hz
Keypad
:
Set directly with
▲▼
keys or the VR on the
keypad
External Input Terminlas:
AI1(0/2~10V), AI2(0/4
~
20mA)input
Multifunction input up/down function(Group3)
Setting
Setting frequency by communication method.
Frequency
Frequency limit
Lower and upper frequency limits
3 skip frequency settings.
Keypad run, stop button
External terminals:
Multi- operation-mode2 / 3 wire selection
Jog operation
Run
Operation set
Run signal by communication method.
V / F curve setting
18 fixed curves and one customized curve
Carrier frequency
1
~
16KHz
Acceleration and
deceleration control
2 off Acc / dec time parameters.
4 off S curve parameters.
Multifunction input
26 functions (refer to description on group3)
Multifunction output
19 functions (refer to description on group3)
Multifunction analog
output
5 functions (refer to description on group3)
Main Control
Features
Main features
Overload Detection,16 preset
speeds,Auto-run,Acc/Dec Switch (2 Stages),Main/Alt
run Command select,Main/Alt Frequency Command
select,PID control, torque boost,
V/F start Frequency,
Fault reset, Firemode.
LED
Display :parameter / parameter value / frequency /
line speed / DC voltage / output voltage / output
current / PID feedback / input and output terminal
status / Heat sink temperature / Program Version /
Fault Log.
Display
LED Status Indicator
Run / Stop / Forward / Reverse ,and etc.
Overload Protection
The relays to protect the motor and the inverter.
(150%/1min)
Over voltage
·220V: >410V ,380V: >820V
Under Voltage
·220V: <190V , 380V: <380V
Momentary Power
Loss Restart
Inverter auto-restart after a momentary power loss.
Stall Prevention
Stall prevention for Acceleration/ Deceleration/
Operation.
Short-circuit output
terminal
Electronic Circuit Protection
Grounding Fault
Electronic Circuit Protection
Protective
Functions
Other protection
features
Protection for overheating of heat sink,The carrier
frequency decreasing with the temperature
function,fault output,reverse prohibit,prohibit for
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......