Group 08- Drive & Motor Protection Functions
No. Description
Range
Factory
Setting
Unit Note
0: Over Torque Detection Disabled
1: Detected After the Setting Frequency
08-13
Over Torque Detection
Control
2: Detected When Running
0 -
0:Stop Output After Over Torque Detection (Free
Run to Stop)
08-14
Over torque protection
action
1:Continue Running After Over Torque
Detection(Display only OL3
)
0 -
08-15
Over Torque Detection
Level
30
~
300
160 -
08-16
Over Torque Detection
Time
0.0
~
25.0
0.1 -
0:Disabled.
08-17
Fire Mode
1:Enabled
0 -
0:Disabled
08-18
Ground Fault
Detection
1:Enabled
1
Notes:Regarding fire mode function, please refer to the conditions below,
1. Before the software rev. 1.1, the fire mode is funtional when 08-17 = 1
2. After the software 1.1,the firemode is functional when 03-00~03-05 =
【
28
】
3. The keypad display will indicate FIrE
4. Under fire mode function, the inverter will run at full speed
Group 09- Communication function setup
No. Description
Range
Factory
Setting
Unit Note
09-00
Assigned Communication
Station Number
1 ~ 32
1 -
*2*3
09-01
RTU/ASCII Code Selection
0:RTU Code
1:ASCII Code
0 -
*2*3
09-02
Baud Rate Setting (bps)
0:4800
1:9600
2:19200
3:38400
2 bps
*2*3
09-03
Stop Bit Selection
0:1
Stop
Bit
1:2 Stop Bits
0 -
*2*3
09-04
Parity Selection
0:Without Parity
1:With Even Parity
2:With Odd Parity
0 -
*2*3
09-05
Data Format Selection
0: 8-Bits Data
1: 7-Bits Data
0 -
*2*3
09-06
Communication Time-Out
Detection Time
0.0 ~ 25.5
0.0 s
09-07
Communication Time Out
Operation Selection
0:Deceleration to Stop
(00-15: Deceleration Time 1)
1:Coast to Stop
2:Deceleration to Stop
(00-17: Deceleration Time 2)
3:Continue Operating
0 -
09-08
Error 6 Verification Time.
1 ~ 20
3
09-09
Drive Transmit Delay Time(ms)
5 ~ 65
5 ms
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......