45
FLUXMASTER 50 INSTRUCTION MANUAL
3. F_19, F_20 = 3: External Emergency Stop
When the external emergency stop signal is activated, the AC drive proceeds to decelerate and stop, (ignoring the stopping
method setting of F_14).The AC drive E.S. light will flash after stopping. After the emergency stop signal is deactivated, turn the
RUN switch OFF and then ON again to cycle it in the terminal mode. (F_10 = 1) Or press the RUN key in the keypad mode (F_10 =
0).The AC drive will then resume operation and restart. If the emergency stop signal is removed before the AC drive stops, the AC
drive will still execute the emergency stop.
4. F_19, F_20 = 4: External Base Block (Immediate Shut Down)
When the external base block signal is activated, the AC drive output will be immediately shut off (ignoring the stopping
method setting of F_14) and flash b.b. Light. After the base block signal is deactivated, turn the RUN switch OFF and then ON
again (F_10 = 1) or press the RUN key (F_10 = 0), the inverter will restart from the original starting frequency.
5. F_19, F_20 = 5: Auto Reset when AC drive faults.
F_21: Multi-Function Output Terminal Control = 1 ~ 3
1. F_21 = 1: Run mode signal
2. F_21 = 2: At Frequency Speed Signal
3. F_21 = 3: Fault signal
Terminals 1 and 2 of TM2 are activated for the following faults: CPF, OL1, OL2, OCS, OCA, OCC, Ocd , Ocb ,OVC , LVC , OHC.
Refer to Section 4 for information on faults.
External Emergency Stop
External Base Block
Summary of Contents for FM50101-X
Page 1: ...www tecowestinghouse com Instruction Manual User Manual...
Page 18: ...External 24V Supply 18 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 33: ...33 FLUXMASTER 50 INSTRUCTION MANUAL 2 6 Mounting Instructions...
Page 53: ...4 Troubleshooting Procedures 53 FLUXMASTER 50 INSTRUCTION MANUAL 4 1 Flow Chart...
Page 54: ...FLUXMASTER 50 INSTRUCTION MANUAL Continued 54...
Page 55: ...FLUXMASTER 50 INSTRUCTION MANUAL Error handling of fault indication of OC OL 55...
Page 56: ...Error handling of fault indication of OV LV 56 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 57: ...57 FLUXMASTER 50 INSTRUCTION MANUAL 1 Motor inoperative...
Page 58: ...FLUXMASTER 50 INSTRUCTION MANUAL 58 2 Motor overheat...
Page 59: ...FLUXMASTER 50 INSTRUCTION MANUAL 3 Unstable motor operation 59...
Page 66: ...Notes 66 FLUXMASTER 50 INSTRUCTION MANUAL...