F_22: Reverse Lockout = 0: REV run command enabled
= 1: REV run command Lockout
NOTE:
When F_04 (motor rotation direction) is set to 1 (reverse), F_22 cannot be set to 1. In order to properly lockout a motor direction,
F_04 must be set at 0 before setting F_22 to 1.
F_23: Auto-restart after Momentary Power Loss = 0: Auto-restart enabled
= 1: Auto-restart disabled
1.
When the AC power supply is temporarily below low voltage protection levels due to low line supply or unusually large
demands on the power supply system, the AC drive will stop immediately. If the voltage level recovers within 2 seconds,
the AC drive can restart by using its speed search program.
2.
When F_23 = 0:
(1) If the momentary power loss is less than 2 seconds, the AC drive resumes operation automatically via speed search at 0.5
seconds after power up.The number of auto restart times is not limited by F_24.
(2) If the momentary power loss is long, the operation of the AC drive is based on the setting of F_10 and the condition of the
external switch.
(3) If the time of momentary loss is between the above two conditions, whether the AC drive will auto-restart depends
on F_24:
F_24 = 0: Auto-restart disabled.
F_24 = 1 ~ 5: Auto-restart enabled 1~5 times.
46
FLUXMASTER 50 INSTRUCTION MANUAL
Summary of Contents for FM50101-X
Page 1: ...www tecowestinghouse com Instruction Manual User Manual...
Page 18: ...External 24V Supply 18 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 33: ...33 FLUXMASTER 50 INSTRUCTION MANUAL 2 6 Mounting Instructions...
Page 53: ...4 Troubleshooting Procedures 53 FLUXMASTER 50 INSTRUCTION MANUAL 4 1 Flow Chart...
Page 54: ...FLUXMASTER 50 INSTRUCTION MANUAL Continued 54...
Page 55: ...FLUXMASTER 50 INSTRUCTION MANUAL Error handling of fault indication of OC OL 55...
Page 56: ...Error handling of fault indication of OV LV 56 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 57: ...57 FLUXMASTER 50 INSTRUCTION MANUAL 1 Motor inoperative...
Page 58: ...FLUXMASTER 50 INSTRUCTION MANUAL 58 2 Motor overheat...
Page 59: ...FLUXMASTER 50 INSTRUCTION MANUAL 3 Unstable motor operation 59...
Page 66: ...Notes 66 FLUXMASTER 50 INSTRUCTION MANUAL...