47
FLUXMASTER 50 INSTRUCTION MANUAL
3.
When F_23 = 1,
(1) Power up after momentary power loss, the AC drive will not start. Even if F_24 > 0.
(2) If the momentary power loss is long, the AC drive must be restarted manually.The operation of the AC drive is based on
the setup of F_10 and the condition of external switch.
4.
When restarting the AC drive, the operation of the AC drive is based on the setup of F_10 (start/stop control) and the
condition of external switches (FWD/REV button).
(1) When F_10 = 0, the AC drive will not restart.
(2) When F_10 = 1 and the external switch (FWD/REV button) is OFF, the AC drive will not restart.
(3) When F_10 = 1 and the external switch (FWD/REV button) is ON, the AC drive will automatically restart.
Attention: Based on safety issues, please turn off the external switch (FWD/REV button) after power loss to avoid possible
damage to personnel and the machine after sudden regeneration of power.
F_24: Number of Auto-Restart Times = 0 ~ 5
1. When F_24 = 0, the AC drive will not auto-restart after a fault recovery. (Except for momentary power
loss, please refer to F_23 for details)
2. When F_24 = 1~5: the AC drive will resume operation via speed search at 0.5 seconds under auto-restart after fault recovery.
(Except for momentary power loss, please refer to F_23 for details).
3. When the AC drive is set to deceleration or DC braking, the transient restart procedure is not performed.
4. If either of following situations should develop, the auto restart times will be reset:
(1) No additional faults (in operation or stop) occurs within 10 minutes.
(2) Press RESET button.
F_25: Restore to Factory Settings
= 010: Constants initialization to 50Hz system
= 020: Constants initialization to 60Hz system
1. When F_25 is set to 010, all parameters are restored to factory settings.The settings of F_05 = 1 and F_06 = 50. F_25 is restored
back to 000 after the reset process is complete. (50Hz operation)
2. When F_25 is set to 020, all parameters are restored to factory settings.The settings of F_05 = 4 and F_06 = 60. F_25 is restored
back to 000 after the reset process is complete. (60Hz operation)
Summary of Contents for FM50101-X
Page 1: ...www tecowestinghouse com Instruction Manual User Manual...
Page 18: ...External 24V Supply 18 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 33: ...33 FLUXMASTER 50 INSTRUCTION MANUAL 2 6 Mounting Instructions...
Page 53: ...4 Troubleshooting Procedures 53 FLUXMASTER 50 INSTRUCTION MANUAL 4 1 Flow Chart...
Page 54: ...FLUXMASTER 50 INSTRUCTION MANUAL Continued 54...
Page 55: ...FLUXMASTER 50 INSTRUCTION MANUAL Error handling of fault indication of OC OL 55...
Page 56: ...Error handling of fault indication of OV LV 56 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 57: ...57 FLUXMASTER 50 INSTRUCTION MANUAL 1 Motor inoperative...
Page 58: ...FLUXMASTER 50 INSTRUCTION MANUAL 58 2 Motor overheat...
Page 59: ...FLUXMASTER 50 INSTRUCTION MANUAL 3 Unstable motor operation 59...
Page 66: ...Notes 66 FLUXMASTER 50 INSTRUCTION MANUAL...