FLUXMASTER 50 INSTRUCTION MANUAL
Routine and Periodical Examination
AC Drive requires routine and periodical examination and maintenance. Carry out the examination only after the " Power LED "
indicator goes off for at least 5 minutes
.
EXAMINATION
Maintenance
Maintenance
Period
Method
Examination
Criterion
Countermeasure
Item
Description
Routine
1 Year
Refer to installation
Temperature: -10~40˚C
Reconfirm environment
❍
instructions and measure
Humidity: under
Improve
Installation Site
temperature and humidity
with thermometer and
95% non-condensing
environment
Environment
hygrometer
Installation site
Check and remove any
❍
Visual inspection
No foreign object
environment
flammable material nearby
Is there any abnormal
AC Drive
vibration on the
❍
Visual and audio Inspection
No foreign object
Tighten loose screws
Installation and
installation site?
Grounding
Is the grounding resistance
❍
Measure resistance by
Resistance under 100
Improve grounding
within acceptable range?
multi-meter
ohm to ground
Input Power
Is the voltage of the primary
❍
Measure voltage by
Voltage level conforming
Improve input
Source Voltage
circuitry normal?
multi-meter
specification
power source
AC Drive
Are the tightened parts secured?
❍
Visual inspection. Use
Terminal
Is there any sign of breakage
❍
screwdriver to verify
Tighten loose
Mounting
on the terminal panel?
screw tightness
No abnormality
screw or return for
Screws
Is there any visible rust?
❍
repair
Internal Wiring
Is it deformed or skewed?
❍
Replace or return
of Inverter
Is the insulation of wire
❍
Visual inspection
No abnormality
for repair
broken?
Heatsink
Is it accumulating dust
❍
Visual inspection
No abnormality
Clean up dust
or dirt?
or dirt
Is it accumulating conductive
❍
PCB
metals or oils?
Visual inspection
No abnormality
Clean up or replace
Is there any overheated or
❍
PCB
burnt components?
Is there any abnormal
❍
Visual and audio
Replace cooling fan
Cooling Fan
vibration or noise?
inspection
No abnormality
Is it accumulating dust
❍
Visual inspection
Clean up
or dirt?
Power
Is it accumulating dust or dirt?
❍
Visual inspection
No abnormality
Clean up
Component
Is there any sign of strange
❍
Capacitor
odor or leakage?
Visual inspection
No abnormality
Replace capacitor
Is there any sign of swelling
❍
or inverter
or bulging?
Summary of Contents for FM50101-X
Page 1: ...www tecowestinghouse com Instruction Manual User Manual...
Page 18: ...External 24V Supply 18 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 33: ...33 FLUXMASTER 50 INSTRUCTION MANUAL 2 6 Mounting Instructions...
Page 53: ...4 Troubleshooting Procedures 53 FLUXMASTER 50 INSTRUCTION MANUAL 4 1 Flow Chart...
Page 54: ...FLUXMASTER 50 INSTRUCTION MANUAL Continued 54...
Page 55: ...FLUXMASTER 50 INSTRUCTION MANUAL Error handling of fault indication of OC OL 55...
Page 56: ...Error handling of fault indication of OV LV 56 FLUXMASTER 50 INSTRUCTION MANUAL...
Page 57: ...57 FLUXMASTER 50 INSTRUCTION MANUAL 1 Motor inoperative...
Page 58: ...FLUXMASTER 50 INSTRUCTION MANUAL 58 2 Motor overheat...
Page 59: ...FLUXMASTER 50 INSTRUCTION MANUAL 3 Unstable motor operation 59...
Page 66: ...Notes 66 FLUXMASTER 50 INSTRUCTION MANUAL...