N3 Drive Operations Manual
Input Fuse Types & Ratings
18
12.0 Input Fuse Types and Ratings
Inverter input fuses are provided to disconnect the inverter from input power in the event of a component failure in the
inverter
’s power circuitry. The inverter’s electronic protection circuitry is designed to clear inverter output short circuits
and ground faults without blowing the inverter input fuses. The table on the next page shows the N3 input fuse ratings.
To protect the inverter most effectively, use fuse types RK5 or CC/T with a current-limit function.
Table 12.1A (1Ø) Input Fuse Types and Ratings
220V class (1Ø)
N3-2
HP
KW KVA
100% CONT
Output AMPS
(A)
Max.RK5
FUSE Rating(A)
Max. CC or T
FUSE
Rating(A)
P5-CS
0.5
0.4
1.2
3.1
10
20
01-CS
1
0.75
1.7
4.5
15
30
02-CS
2
1.5
2.9
7.5
20
40
03-CS
3
2.2
4.0
10.5
25
50
Table 12.1B (3 Ø) Input Fuse Types and Ratings
220V class (3 Ø)
N3-2
HP
KW KVA
100% CONT
Output AMPS
(A)
Max.RK5
FUSE Rating(A)
Max. CC or T
FUSE
Rating(A)
P5-C
0.5
0.4
1.2
3.1
8
10
01-C
1
0.75
1.7
4.5
12
15
02-C
2
1.5
2.9
7.5
15
20
03-C
3
2.2
4.0
10.5
20
30
05-C
5
3.7
6.7
17.5
30
50
07-C
7.5
5.5
9.9
26
50
60
10-C
10
7.5
13.3
35
60
70
15-N1
15
11.0 20.6
48
80
100
20-N1
20
15.0 27.4
64
100
125
25-N1
25
18.5 34.0
80
125
150
30-N1
30
22.0 41.0
96
160
200
40-N1
40
30.0 54.0
130
200
250
NOTES:
Cont.