N3 Drive Operations Manual
Keypad Functions & Navigation; Key Functions
23
17.0 Keypad Key Functions and Navigation
The N3 keypad, provides all the necessary functions to allow full control of the N3 inverter. The keypad has
membrane type keys and a 7 - segment 4 - digit LED display. Also located on the keypad is a potentiometer that can
be used to control inverter output frequency when selected as the control source. A
remote
keypad is available as an
option
, and is covered more in detail in the
Option Modules
Sec. 20.0
.
17.1 N3 Keypad
Output frequency
control potentiometer
(when selected)
4 digit 7 segment
LED display
Membrane keys
LED indicators
LED indicators
Fig. 17.1 N3 Keypad
17.2 Keypad LED Functions
Table 17.1
LED
STATUS
DESCRIPTION
SEQ
(Sequence
OFF
Run Command Source is from the
keypad
(b000=0000)
(factory default)
ON
Run Command Source is from
external terminal
(b000=0001),
or
RS485 communication
control
(b000=2)
FRQ
(Frequency)
OFF
Frequency Command Source is from the
keypad
(b004=0000) (factory default)
ON
Frequency Command Source is from
potentiometer
on
keypad
(b004=1),
external analog signal
(b004=0002),
up /
down frequency control using MFIT (S1-S6)
(b004=0003) or
RS485 communication control
(b004=0004)
*FWD
(Forward)
ON
Drive is running in the
forward
direction
Flashing
Drive is in the
stop mode
REV
(Reverse)
ON
Drive is running in the
reverse
direction
Flashing
Drive is in the
stop mode
FUN
(Function)
ON
Entering
A
or
b
parameters
*Hz/RPM
ON
Display is showing
output frequency
VOLT
ON
Display is showing
motor voltage
(b014=0001),
DC bus
voltage
(B015=0001) or
PID feedback voltage
(b016=0001)
AMPS
ON
Display is showing
motor current
(b013=0001)
*Note
– On initial powerup (factory default), the only LEDs that are on are Hz/RPM and FWD.