N3 Drive Operations Manual
b (Basic) Parameter Details; b005
– b014
32
b005
Frequency Upper limit
0.01 - 400.00 (Hz)
b006
Frequency Lower limit
0.01 - 400.00 (Hz)
Fig. 19.3
Note: When b006 = 0 Hz and the frequency command is 0 Hz, the inverter will stop at 0 speed. When b006 > 0 Hz
and the frequency command ≤ b006, the frequency output will be the b006 preset value.
b009
is the parameter for the V/f pattern selection (0
– 18) and will be covered extensively in the
A
(advanced)
parameter section. (A129 ~ 137 and Fig. 19.27)
b010 = 0000: Disable parameter lock.
b010 = 0001: Enable parameter lock.
Note:
Message
“LOC” will be displayed if an attempt is made to program when enabled.
b011 Advanced Display
0000: Disable
0001: Enable
b011 = 0000: Disable advanced display.
b011 = 0001: Enable access to advanced functions (A000 - A181).
Note: The b012 function is only available for products with an LCD keypad (option). The function is not valid for
the LED keypad.
b013
Motor Current Display Selection
0000:
Disable Motor Current Display
0001: Enable Motor Current Display
b014 Motor Voltage Display Selection
0000:
Disable Motor Voltage Display
0001: Enable Motor Voltage Display
Cont.
b010
Parameter Lock (except b010)
0000: Disable
0001: Enable
b012
Language Selection
0000: English
0001: German
0002: French
0003: Italian
0004: Spanish
b005 (Frequency upper limit)
b006 (Frequency lower limit)
Frequency command
O
u
tp
u
t f
re
q
u
e
n
c
y
(see note below)
b005 & b006 (Frequency Reference Limits)