N3 Drive Operations Manual
A (Advanced) Parameter Summary; A000
– A017
34
19.3 A (Advanced) Parameter Summary
Cont.
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A000
Control Mode Control Mode
0000: Vector (Constant Torque)
0001: Vector (Variable Torque)
0002: Volts/Hz
0002
A001
Motor Rated
Volt
Motor Rated Voltage
(Vac)
Refer to Appendix B Table for default values
5
A002
Motor Rated
Amps
Motor Rated Current
(Amp)
5
A003
Motor Rated
HP
Motor Rated Power
(HP)
5
A004
Motor Rated
RPM
Motor Rated Speed
(RPM)
5
A005
Motor Rated
Hz
Motor Rated
Frequency (Hz)
5
A006
Auto Tuning
Motor Parameter
Auto Tuning
0000: Disabled
0001: Enabled
0000
A007
AC Input Volt
AC Line Input
Voltage (Vac)
230V SERIES: 170.0 - 264.0
460V SERIES: 323.0 - 528.0
230V
460V
A008
A009
Reserved
Reserved
A010
Keypad Stop
Keypad Stop Button
(In External
Run/Stop Mode)
0000: Stop Button Enabled
0001: Stop Button Disabled
0000
A011
Keypad
Up/Down
Keypad Frequency
Setting with
Up/Down Keys in
Run Mode
0000:
‘Enter’ must be pressed after
frequency change with
Up/Down Keys on keypad.
0001: Frequency will be changed
directly when Up/Down Keys
are pressed.
0000
A012
Starting
Method
Starting Method
Selection
0000: Normal Start
0001: Enable Speed Search
0000
A013
PwrL Selection
Momentary Power
Loss and Restart
0000: Momentary power loss and
restart disable
0001: Momentary power loss and
restart enable
0002: Momentary power loss and
restart enable while CPU is
still powered up.
0000
A014
PwrL Ridethru
T
Momentary Power
Loss Ride-Thru
Time (Seconds)
0.0 - 2.0
0.5
A015
Dir Start Sel
Direct Run After
Power-Up
0000: Enable Direct run after
power- up
0001: Disable Direct run after
power-up
0001
A016
Dir Start Delay
Delay-ON Timer
(Seconds)
0.0 - 300.0
0.0
A017
Auto Restart Auto Restart Method
0000: Enable Speed Search
0001: Normal Start
0000