N3 Drive Operations Manual
A (Advanced) Parameter Summary; A018
– A039
35
* MFIT refers to Multi-Function Terminal Inputs.
Cont.
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A018
Auto Restart
Sel
Number of Auto
Restart Attempts
0 - 10
0
A019
Auto Restart
Delay
Auto Restart Delay
Time (Seconds)
0.0 - 800.0
0.0
A020
Reset Mode
Sel
Reset Mode Setting
0000: Enable Reset Only when Run
Command is Off
0001: Enable Reset when Run
Command is On or Off
0000
A021
A022
Reserved
Reserved
A023
S-Curve 1
S-Curve Acc/Dec #1
(Seconds)
0.0 - 4.0
0.2
A024
S-Curve 2
S-Curve Acc/Dec #2
(Seconds)
0.0 - 4.0
0.2
A025
Accel Time 2
Acceleration Time
# 2 (MFIT)*
(Seconds)
0.1
– 3600.0
10.0
1
A026
Decel Time 2
Deceleration Time
# 2 (MFIT)*
(Seconds)
0.1
– 3600.0
10.0
1
A027
Jog Acc Time
Jog Acceleration
Time (MFIT)
*
(Seconds)
0.1 - 25.5
0.5
1
A028
Jog Dec Time
Jog Deceleration
Time (MFIT)*
(Seconds)
0.1 - 25.5
0.5
1
A029
DC Inj Freq
DC Injection Braking
Start Frequency
(Hz)
0.1 - 10.0
1.5
A030
DC Inj Level
DC Injection Braking
Level (%)
0.0
– 10.0% (Level 100% by based
on Motor Rate Voltage A001)
5.0
A031
DC Inj Time
DC Injection Braking
Time (Seconds)
0.0 - 25.5
0.5
A032
Skip Freq 1
Skip Frequency # 1
(Hz)
0.00 - 400.00
0.0
1
A033
Skip Freq 2
Skip Frequency # 2
(Hz)
0.00 - 400.00
0.0
1
A034
Skip Freq 3
Skip Frequency #
3 (Hz)
0.00 - 400.00
0.0
1
A035
Skip
Bandwidth
Skip Frequency
Bandwidth (± Hz)
0.00 - 30.00
0.0
1
A036
A037
A038
(Reserved)
Reserved
A039
Parameter
Lock
Parameter Lock
0000: Enable all Functions
0001: A059
– A068 cannot be
changed
0002: All Functions Except A059
–
A068 cannot be changed
0003: Disable All Functions
0000