N3 Drive Operations Manual
A (Advanced) Parameter Summary; A050
– A057
37
Cont
.
NOTES:
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A050
S1 Terminal
Sel
Multifunction Input
Term. S1
0000: Forward/Stop Command
0001: Reverse/Stop Command
0002: Frequency Command 2
(A062)
0003: Frequency Command 3
(A063)
0004: Frequency Command 4
(A065)
0005: Jog
0006: Acc/Dec # 2
0007: Emergency Stop A Contact
0008: Base Block A Contact
0009: Speed Search
0010: Energy Saving
0011: Control Signal Selection
0012: Communication Selection
0013: Acc/Dec Disabled
0014: Up Command
0015: Down Command
0016: Master/Auxiliary Speed
0017: PID Function Disabled
0018: Reset
0019: Pulse Input terminal
( terminal S5 )
0020: PID feedback signal AI2
( terminal *AI2)
0021: AI2 Bias signal 1 input
( terminal *AI2)
0022: AI2 Bias signal 2 input
( terminal *AI2)
0023: Analog input (terminal AIN)
0024: Multi-Sequence Control
0000
*7
A051
S2 Terminal
Sel
Multifunction Input
Term. S2
0001
A052
S3 Terminal
Sel
Multifunction Input
Term. S3
0002
A053
S4 Terminal
Sel
Multifunction Input
Term. S4
0003
A054
S5 Terminal
Sel
Multifunction Input
Term. S5
0004
A055
S6 Terminal
Sel
Multifunction Input
Term. S6
0018
A056
AIN Term Sel
Multifunction Input
Term. AIN
0023
*0025: Emergency Stop B Contact
(NC)
*0026: Base Block B Contact (NC)
A057
Term Scan
Time
Multifunction Input
Term. S1 - S6
Signal Verification
Scan Time
(mSec X 4 )
1
– 100 (4-400msec)
5(20ms)