N3 Drive Operations Manual
A (Advanced) Parameter Summary; A118
– A130
42
.
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A118
Dec Trip Time
Deceleration Time
In Trip Prevention
Mode (Seconds)
0.1
– 3600.0
3.0
A119
Motor OL1 Sel
Electronic Motor
Overload
Protection
Operation Mode
0000: Enable Electronic Motor
Overload Protection
0001: Disable Electronic Motor
Overload Protection
0000
A120
Motor Type
Motor type
Selection
0000: Electronic Motor Overload
Protection Set for Non-Inverter
Duty Motors
0001: Electronic Motor Overload
Protection Set for Inverter Duty
Motors
0000
A121
Motor OL1
Curve
Motor Overload
Protection Curve
Selection
0000: Curve A (OL =103 %) (150 %
for 1 Minute)
0001: Curve B (OL = 113 %) (123 %
for 1 Minute)
0000
A122
Motor OL1
Operat
Operation After
Overload
Protection
is Activated
0000: Coast-to-Stop After Overload
Protection is Activated
0001: Drive Will Not Trip when
Overload Protection is Activated
(OL1)
0000
A123
Torq Det Sel
Over/Under torque
Detection
Selection
0000: Disable Over/Under torque
Operation
0001: Enable Over/Under torque
Operation Only if at Set
Frequency
0002: Enable Over/Under torque
Operation while the Drive is in
Run Mode
0000
A124
Torq Det Res
Operation After
Over/Under torque
Detection is
Activated
0000: Drive will Continue to Operate
After Over-torque is Activated
0001: Coast-to-Stop After Over-
Torque is Activated
0000
A125
Torq Hi Level
Over-torque
Threshold Level
(%)
30
– 200 (Level 100% based by
Motor HP A003)
150
A126
Torq Hi Delay
Over-torque
Activation Delay
Time (Seconds)
0.0 - 25.0
0.1
A127
Torq Lo Level
Under-torque
Threshold Level
(%)
30-200 (Level 100% based by Motor
HP A003)
0
A128
Torq Reserv
Time
Under-torque
Activation Delay
Time (Seconds)
0.0
– 25.0
0.1
A129
Torque Boost
Volts/Hz Curve
Modification
(Torque Boost) (%)
0
– 50.0
0.0
1 & 6
A130
Motor noLoad
Amp
Motor No Load
Current (Amps
AC)
-----
0
5 & 6
Cont.