N3 Drive Operations Manual
A (Advanced) Parameter Details; A057
– A068 Co
nt
. & A060
58
Function
Code No.
LCD
Display
Description
Range/Code
Factory Setting
A059
(Jog Freq)
Jog Frequency (Hz)
0.00 - 400.00
2.00
A061
(Freq Command 1)
Frequency Command 1 (Hz)
0.00 - 400.00
5.00
A062
(Freq Command 2)
Frequency Command 2 (Hz)
0.00 - 400.00
5.00
A063
(Freq Command 3)
Frequency Command 3 (Hz)
0.00 - 400.00
10.00
A064
(Freq Command 4)
Frequency Command 4 (Hz)
0.00 - 400.00
20.00
A065
(Freq Command 5)
Frequency Command 5 (Hz)
0.00 - 400.00
30.00
A066
(Freq Command 6)
Frequency Command 6 (Hz)
0.00 - 400.00
40.00
A067
(Freq Command 7)
Frequency Command 7 (Hz)
0.00 - 400.00
50.00
A068
(Freq Command 8)
Frequency Command 8 (Hz)
0.00 - 400.00
60.00
Priority in reading the frequency: Jog > Preset speed > Keypad frequency or external frequency signal
Multifunction
terminal 3
Preset value=04
Multifunction
terminal 2
Preset value=03
Multifunction
terminal 1
Preset value=02
Jog Command
terminal
Preset value=05
Output
frequency
preset value
0
0
0
0
A061
x
x
x
1
A059
0
0
1
0
A062
0
1
0
0
A063
0
1
1
0
A064
1
0
0
0
A065
1
0
1
0
A066
1
1
0
0
A067
1
1
1
0
A068
A060 Step of Up/Down Function (Hz)
0.00
– 5.00 Hz
1.) A060 = 0.00: When the Up terminal is ON, the frequency continuously increases while the Down terminal is
ON, the frequency continuously decreases until the upper and lower frequency limits are reached.
(See fig. below)
ON
ON
OFF
OFF
UP
DOWN
O
ut
pu
t F
re
qu
en
cy
Up / Down Profile Example A060=0.00
b005 Upper
frequency limit
b006 Lower
frequency limit
Reaches Upper
frequency limit
Fig. 19.10