N3 Drive Operations Manual
Environment & Installation; Inverter Mounting
6
4.0 Environment and Installation
The environment will directly affect the proper operation and the life span of the inverter. To ensure that the inverter
will give maximum service life, please comply with the following environmental conditions:
4.1 Inverter Mounting
When mounting and installing one or more inverters on a panel or in an enclosure, ensure that the placements and
clearances are correct
. (see Fig.’s 4.1.1 and 4.1.2). Also make sure that the inverter(s) are mounted
vertically
to
maximize air flow to the heatsink. To further increase airflow, the dust cover on the inverter(s) may be removed,
provided that the environment is free from contaminants.
PANEL
Correct
Fan
Fan
Enclosure
Enclosure
PANEL
Incorrect
Correct
Incorrect
N3
N3
N3
N3
N3
N3
Panel Mounting
Enclosure Mounting
Fig. 4.1.1 Panel and Enclosure Placements
Cont.
Ambient Temperature: 14 -104
o
F (-10
o
C - +40
o
C),
Without Cover: 14-122
o
F (-10
o
C - +50
o
C)
Relative Humidity: 95% non-condensing
Altitude : < 3,281 ft. (1000m)
Avoid exposure to rain or moisture.
Avoid direct sunlight.
Avoid oil mist and salinity.
Avoid corrosive liquid and gas.
Avoid dust, lint fibers, and small metal
filings.
Keep away from radioactive and
flammable materials.
Avoid electromagnetic interference (soldering machines, power machines).
Avoid vibration (stamping, punching machines etc.). Add a vibration-proof pad if the
situation cannot be avoided.
If several inverters are placed in the same control panel, provide a heat removal means
to maintain ambient temperatures below 40
o
C.