Chapter 6 FBD Block Diagram Programming
185
MU mode2: Write single register
Setting communication address is constant:
Mode2
FBD display
Parameter display
Enable Input
→
←
Slaver ID
←
Register address
Parameter
→
←
Source data address
Setting communication address is data register DR:
Mode2
FBD display
Parameter display
Enable Input
→
←
Slaver ID
←
Register address
Parameter
→
←
Source data address
Address is constant 0003,
Setting data DRE0=1234 (hex: 04D2),
Send data:
01 06 00 03 04 D2 CRC16;
Received response from slave1:
01 06 00 03 04 D2 CRC16
;
Setting address DR03=0001,
Setting data DRE0=1234 (hex: 04D2),
Send data:
01 06 00 01 04 D2 CRC16;
Received response from slave1:
01 06 00 01 04 D2 CRC16;