Chapter 3 Expansion unit specification
expansion unit
3-21
2.5.2
TP03-8AD Specification
Specification
Item
Voltage Current
Analog input range
0V~10V or 1V~5V ,
Input impedance 30K
Ω
0mA~20mA or 4mA~20mA ,
Input impedance 250
Ω
Data range
0000(0V)~4000(10V)or
0000(1V)~2000(5V)
0000(0mA)~2000(20mA)or
0000(4mA)~2000(20mA)
Resolution 2.5
mV
10
μ
A
Accuracy
±1% or less(at 25 )
℃
±1%or less(at 0~55 )
℃
Transmit speed
1scan time/ 8 Channel
A0~A7
Analog input terminal
C0~C7
Common terminal for A0~A7
SHLD
Please connect Shielded terminal to
FG on the House. And all shielded
terminals are internally connected.
24V
24VDC input te)
Terminal
block
0V 24VDC
input
terminal(-)
I A0:
Current
input
S0
V A0:
Voltage
input
:
I A7:
Current
input
Voltage /Current input
switch
S7
V A7:
Voltage
input
Power indicator
PWR:+24 V Power LED(Green)
LNK: Link LED(Green)
Internal power
5VDC:Max current 30mA
A4
shld
shld
C4 C5 C6 C7
A6
A5
A7
A0
+24V
0V
A3
A2
A1
C3
PWR
C1
C0
C2
LNK
Outline figure
External power
24VDC±10% (Consumption current: Max 50mA)
Accessory
Installation manual, Expansion cable(TP03-304EC : 6cm, 26pin)
Principle
figure