Chapter 3 Expansion unit specification
expansion unit
3-24
2.5.5
TP02-2DA+ Specification
Specification
Item
Voltage Current
Analog output range
0V~10V or 1V~5V, external impendence
should be less than 500
Ω
0mA~20mA or 4mA~20Ma, Principle
figure 500
Ω
.
Data range
0000(0V)~4000(10V) or
0000(1V)~2000(5V)
0000(0mA)~2000(20mA) or
0000(4mA)~2000(20mA)
Resolution 2.5
mV
10
μ
A
Accuracy
±5% or less (at 25 )
℃
±1% or less (0~55 )
℃
Transmit speed
1scan time/ 4 Channel
V1~V2 Voltage output terminal, input voltage
signal between VC
C1~C2 Common
ground
V1±~V2±
Voltage output terminal, output voltage
signal (-10V~+10V)between V and C
terminal (V1,V2 and V1±,V2± can not
be used at same time)
C3~C4 Common
ground
I1~I2
output terminals for Current signal
between I,C .
SHLD
Please connect Shielded terminal to FG
on the House. And all shielded terminals
are internally connected.
24V
24VDC Power input te)
Terminal
block
0V 24VDC
Power
input terminal(-)
Power indicator
LED (5V power LED: Green)
Internal power supply
5VDC:Max current 50mA
V1
V2 C4
C3
SHLD
SHLD
Power
11
0V
+24V V1
12
SHLD
SHLD
V2
C1
C2
Outline figure
External power
24VDC±10%(Consumption current: Max 100 mA)
Accessory Installation
manual,
Expansion cable(TP-042EC : 4cm
,
14pin)
Principle
figure