AG-300 Plus Gateway User Manual
RS485 Pin Assignment of Inverter RJ-45 and Connect to AG-300 Plus
1
2
3
4
5
6
7
8
Data+ Data –
Data+ RSV.
RSV. Data –
5V
GND
RS485 Pin Assignment of Inverter RJ-45
Parameter Setting Description:
The following is the 510 series inverter parameter setting:
00-02 (Main operate command
source)
0 (Key panel)
00-05 (Main frequency command
source)
3 (Communication control) for
5 (Communication control) for L510s/E510
09-00 (Communicator station)
1 (Subject to AG300 setting)
09-01 (Communication mode
selection)
0 (MODBUS)
09-02 (Baud rate setting)
3 (9600bps) for A510s/F510/E510s
1 (9600bps) for L510ss/E510
09-03 (Stop bit selection)
0 (1stop bit)
09-04 (Parity bit selection)
0 (No parity bit)
09-05 (Data bit selection)
0 (8-bit data)