7
FO 935 ETH
TECHNICAL SPECIFICATIONS
FO 935 ETH
TESTS AND PERFORMANCE
●
Construction in compliance with the EC regulations
●
Protection from electrical interferences EN 61000-4-4
●
Dielectric strength 1500 VAC for 1 min. between output relay and FO IN input, relay and
power supply, and FO IN input and power supply
●
Reading range:-35°C to +195°C
●
Interface precision1% vfs, ±1 digit
●
Ambient operating temperature from
–20°C to +60°C
●
Permitted humidity 90% without condensate
●
Polycarbonate frontal film IP65
●
Container NORYL 94 _V0
●
Absorption 7.5VA
●
Self-diagnostic circuit
●
Electronic part protective treatment
Optional
DISPLAY AND DATA MANAGEMENT
2 x 13 mm displays with 3 digits to display temperatures, messages and channels
●
3 LEDs to display the state of the alarms of the selected channel
(ALARM-TRIP-FAULT)
●
4 LEDS selection of display mode
(SCAN-AUTO-MAN-T.MAX)
●
2 LEDs to display the state of FAN1 and FAN2
●
Temperature control from 1°C to 190°C (alarms)
●
2 alarm thresholds for channels 1-2-3
●
2 alarm channels for channel 4
●
2 ON-OFF thresholds FAN 1 and FAN 2 ventilation
●
FO sensor diagnostics (FCC-FOC-FLT)
●
Data memory diagnostics (Ech)
●
Communication diagnostics FO 935 to CFO 521 (TEC)
●
Access to programming through front keyboard
●
Automatic exit from programming, display and relay test after 1 minute of inactivity
●
Incorrect programming warning
●
Selection between channels automatic scanning, hottest channel or manual scanning
(SCAN-AUTO-MAN)
●
Storage of maximum temperatures reached by channels and alarm status (TMAX)
●
Front key to reset the alarms
●