A LOOK AT SER
VICE SAF
ETY
Compressor Motor and Component Inf
o
rmation
23
C.
“AN”
W
iring on
T
ypical 460
V
o
lt System with Electr
onic Pr
otection Module
2 Speed Motor
Connections
Line Voltage
C'Case Heaters
T
1
T
2
T
3
L
1
M
1
T
1
M
2
SS
1
T
2
L
2
L
3
*Contactor
460-60-3
# 14 Min.
Transformer
460V Input
230V Output
230V
460V
Run New Lead From M
1
To Contactor Coil
Remove Existing Lead At
Contactor Coil And Connect To M
2
# 14 Min.
See Table 3-4
Use Copper Conductors Only
24 Volt
Compressor
Sensors
Compressor
Power
To
Control
Circuit
Control Line
230V
15AA1104C
Electronic Protection Module
S
1
C
1
L
1
L
2
L
3
R
1
R
2
R
3
C
2
S
Table 3-4: "AN" Wiring on Typical 460 Volt System
Model
AN5590E/F
AN5610E/F
AN5612E/F
AN5614E/F
#12 TW
#12 TW
#10 TW
#10 TW
92,500
100,000
122,000
140,000
14
14.5
18
21
86
93
116
135
RLA
LRA
Capacity
BTU/HR
20 A
20 A
25 A
30 A
Min.
Cont.*
Size
Min.
Cond.
Size
*Contactor ampere rating is at compressor rated voltage.
# 14 Min.
Figure 3-13.
“AN” wiring on typical 460 volt system with electronic protection module.