Step 5: Check Module PTC Relay
Check the relay by measuring continuity between the starting
and protector package pin holes where the R and S pins on the
compressor are inserted. If there is no continuity, the relay may
be open. Wait 3 minutes, then check continuity again. If there is
still no continuity, replace the protector package.
Step 6: Continue Troubleshooting
If all above tests prove satisfactory and unit still fails to operate
properly, check for adequate compressor pumping as outlined in
the procedure on page 83.