46
XR20C/XR02C/REK31E Coolers without defrost
XR20C
code
XR02
code
REK31
code
PARAMETER
Set Set d1
Main Set point
4°C
Hy Hy d2
Differential ( hysteresis )
2°C
LS LS d3
lower limit of main set point
-2°C
US US d4
Upper limit of main set point
10°C
AC AC
3min
d5
Minimum time interval between the disactivation and successive activation on compressor
180s
ALU AU d6
Max temperature alarm differential
50°C
ALd Ad d7
Maximum or minimum temperature alarm delay
99
IdF Id d8
Time interval between defrost cycle
6h
MdF Md d9
Max defrost cycle time
1min
dtE dE
8°C
d10
Defrost –end temperature
12°C
d11
Time interval for supplementary defrost cycles
2min
dAd d12
Real temperature display delay at defrost end
30 min
d13
Compressor function during defrost
0
d14
Dripping time
1min
Ot Ot
0
d19
Offset ?
-6°C
CF CF
°C
d22
Unit of measure
0
d23
Compressor function during probe failure
2
COn Cy d24
Compressor on-time during probe failure
10 min
COF Cn d25
Compressor off-time during by probe failure
10 min
d27
Serial line address
0
ALL AL d38
Minimum temperature alarm differential
40°C
P2P P2
Evaporator probe presence
N
OE OE
Evaporator probe calibration
0
OdS Od
Outputs delay at start up
2min
CCt
Continuous cycle duration
0
rES rE Resolution
dE
Lod Ld Probe
displayed
P1
dFd dF
Displaying during defrost
SEt
dAF
Defrost delay after fast freezing
0