Wireless system (CORA)
16
Relaying wireless signals
CORA devices can relay signals from other devices. All required settings for this are carried out at
the device, which transmits the signal to be relayed. Pairing with devices that simply relay signals is
not required.
During parameterisation of the CORA device, simply enter the CORA ID of the relaying devices under
the items
HOP1-3
(depending on how many relays should occur).
RCV-DL, GBS-F and RAS-F devices
cannot
be used.
Example:
The
CORA 1
device should control the
CORA 3
wirelessly, but cannot reach it due to the
local conditions. However,
CORA 1
can reach
CORA 2
, and
CORA 2
can reach
CORA 3
.
During parameterisation on
CORA 1
(= pairing with
CORA 3
), the CORA ID
of
CORA 3
is entered under
CORA ID
, and the CORA ID of
CORA 2
is en-
tered under
HOP1
.
No settings are required on
CORA 2
. This device relays the signals inde-
pendently.
No settings are required on
CORA 3
either.
The only change to the pairing process is that CORA IDs are entered under
HOP1-3
.
To enable additional devices to relay the signal, they should be specified in the corresponding order
under
HOP2
and then under
HOP3
. A data packet is sent by the transmitter to HOP1, HOP2, HOP3
and then to the target device (= "CORA ID"), where defined.
The entry
00000000
means that no relaying will occur.
Deleting a pairing
Under the tab
FiD
is the item
Delete CORA device
.