Sequence of Operation

 tekmarNet

®

 System 

Section A

tekmarNet

®

 is a family of products that use communication 

to operate the HVAC system in a comfortable and efficient 
manner. The Wiring Center is a zoning component in 
a tekmarNet

®

 system and requires tekmarNet

®

4 (tN4) 

Thermostats to be directly connected to it.

The tekmarNet

®

4 (tN4) Expansion terminals can link the 

Wiring Center with other tekmarNet

®

 components:

House Controls 400, 401, 402, 403 - Provides boiler and 
DHW control

Reset Modules 420, 421, 422, 423
Boiler Controls 274, 275
Wiring Centers 313, 314, 315, 316 - Add additional zones
tN4 Thermostats - Add thermostats
tN4 Timer 033 - Adds 4 programmable schedules
tN4 User Switch 479 - Provides a system override for 
vacations and holidays
tN4 Setpoint Control 161, 162 - Control hot tubs, pools 
and more






ZONE 1

The zone 1 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 2

The zone 2 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 3

The zone 3 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 4

The zone 4 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 5

The zone 5 thermostat is calling for heat 
and the 24 V (ac) output is energized.

ZONE 6

The zone 6 thermostat is calling for heat 
and the 24 V (ac) output is energized.

POWER

24 V (ac) is being applied to the Wiring 
Center to provide it with power.

END SWITCH / ZONE GROUP PUMP

At least one of the zone thermostats are 
calling for heat and the end switch and zone 
group pump relay outputs are closed. 

LEDs

User Interface

Power

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

Zone 6

End Switch / Zone Group Pump

Wiring Center 315

Summary of Contents for D 315

Page 1: ...tats and zone valves while only requiring two wires to be run back to the mechanical room When combined with tekmarNet 4 Thermostats all devices communicate to provide a synchronized end switch that r...

Page 2: ...nnel for servicing There are no user serviceable parts Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death Installation The instal...

Page 3: ...nably close proximity to the equipment All line voltage wire connections are recommended to be pulled inside a flexible or solid conduit Always follow proper wiring practices building and electrical c...

Page 4: ...utral wires to the 115 V ac side of the transformer Use a wire nut or approved connector See Figure 1 Wire the Power L Connect the 115 V ac line voltage L wire to the 115 V ac side of the transformer...

Page 5: ...W ter minals on the 315 Low Voltage Wiring The enclosure may be mounted directly to a wall or to an electrical junction box Ensure that the high voltage wires are neatly tucked inside the electrical...

Page 6: ...oltage through the ther mostat See the thermostat installation manual for details Testing the Zone Output 1 Use an electrical test meter to measure the ac voltage between the C and the Vlv terminals f...

Page 7: ...C Zone 5 R W tN4 C Zone 6 R H8001B End Switch Use at least 167 F 75 C conductors Description tN4 Wiring Center 315 six tekmarNet 4 Thermostats and six zone valves wired to a tekmar System Control 420...

Page 8: ...ne 3 W tN4 R C Zone 4 W tN4 R tN4 Wiring Center 315 Six Zone Valves W tN4 C tN4 C X Zone 1 Expansion Vlv C Zone 1 Vlv C Zone 2 Vlv C Zone 3 Vlv C Zone 4 Vlv C Zone 5 Vlv C Zone 6 X C Input Power R R W...

Page 9: ...Pump C Zone 2 W tN4 R C Zone 3 W tN4 R C Zone 4 W tN4 R tN4 Wiring Center 315 Six Zone Valves W tN4 C tN4 C X Zone 1 Expansion Vlv C Zone 1 Vlv C Zone 2 Vlv C Zone 3 Vlv C Zone 4 Vlv C Zone 5 Vlv C Zo...

Page 10: ...ations and holidays tN4 Setpoint Control 161 162 Control hot tubs pools and more ZONE 1 The zone 1 thermostat is calling for heat and the 24 V ac output is energized ZONE 2 The zone 2 thermostat is ca...

Page 11: ...ng on each thermostat Zone Synchronization Another feature of the Wiring Center is Zone Synchronization In typical zoned systems the thermostats operate on a stand alone basis This means that a zone t...

Page 12: ...y Purchaser to its customers which are different from or in excess of the tekmar Lim ited Warranty are the Purchaser s sole responsibility and obligation Pur chaser shall indemnify and hold tekmar har...

Reviews: