background image

Step Four

Testing and connecting the wiring

Caution

These tests are to be performed using standard testing practices and procedures and should only be carried out by properly
trained and experienced persons. A good quality electrical test meter, capable of reading from at least  0 — 200 Volts ac, and
at least 0 — 2,000,000 Ohms, is essential to properly test this control. At no time should voltages in excess of 28 V ac be
measured at any of the wires connected to the control.

Test the sensors

• This test must be performed

 before power is applied to the control and before the sensors are connected to the terminal strip.

Test the sensors according to the instructions printed in the enclosed Data Brochure D 001.

Test the power supply

• Ensure exposed wires are not grounded or in contact with other wires. Turn on the 24 V ac power supply and, using an AC

voltmeter, you should measure between 20 and 28 volts at the secondary side of the transformer.

• Turn off the power and complete the electrical connections to the terminal strip of the control.

Power and output connections

The installer should test to confirm that no voltage is present at any of the wires.

• Connect the power supply to terminals 

Power C — R  (1 and 2).

• Connect the heating device circuit to terminals

 Heat  (3 and 4).

• Connect the system circuit to terminals

 System (5 and 6).

Sensor connections — Caution, voltage is never applied to these terminals

• Connect the Slab Sensor 072 to terminals

 Com Sen and Slab Sen (7 and 8).

• Connect the Outdoor Sensor 070 to terminals

 Com Sen and Out Sen  (7 and 9).

2

Caution

Improper installation and operation of this control could result in damage to the equipment and possibly even
personal injury.  It is your responsibility to ensure that this control is safely installed according to all applicable codes
and standards. This electronic control is not intended for use as a primary limit control. Other controls that are
intended and certified as safety limits must be placed into the control circuit.

Step One

Getting ready

Check the contents of this package.  If any of the contents listed are missing or damaged, please refer to the Limited Warranty
and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance.

Type 650 includes:

• One Snow Melting Control 650  •  One Slab Sensor 072  •  One Outdoor Sensor 070
• One Data Brochure D 650  •  One Data Brochure D 001  •  Application Brochures A 650

Other information available:

• Essay E 000, Essay E 600

N

ote: Carefully read the Sequence of Operation section in this brochure to ensure that you have chosen the proper control and

understand its functions within the operational requirements of your system.

Step Two

Mounting

The control is mounted in accordance with the instructions in the Data Brochure D 001.

Step Three

Rough-in wiring

All electrical wiring terminates in the two wiring chambers at the bottom front of the control.  If the control is to be mounted on
an electrical box, the wiring can be roughed-in at the electrical box prior to installation of the control (see Brochure D 001).
Standard 18 AWG solid wire is recommended for all low voltage wiring to this control.

Installation

• Install the Outdoor Sensor 070 according to the instructions in Data Brochure D 001 and run the wiring back to the control.

Do not connect the wires to the terminals yet.

• Install the Slab Sensor 072 in the slab halfway between the heating pipes or electric

cables and within 1 inch of the slab surface (see adjacent diagram). The sensor
should be placed approximately 3 feet (1m) from the edge of the slab. Run the wiring
back to the control but do not connect the wires to the terminals yet.

• Install a 24 V ac Class II transformer with a minimum 5VA rating and run the wiring

from the transformer to the control. 

A Class II transformer must be used. Do not

connect either of the transformer secondary wires to ground.

• Run wiring from the heating device and system circuits to the control.

1" (25mm)

halfway between the
pipes or electric cables

Slab Sensor

SLAB

 

Power should not be applied to any of the wires during the rough-in wiring stage.

24 V Only

Do not apply

power here

24 V ac

power 

supply

Heat Relay

closes to turn on

heating device

System Relay 

closes when in 

melting or idling 

modes

1

C

2

R

3

4

10A

10A

Heat

System

5

6

Slab

Sen

Out

Sen

8

9

Slab

Sensor

072

Outdoor

Sensor 

070

Power

7

Com

Sen

Summary of Contents for D 650

Page 1: ... slab at the Melting temperature The method used to cycle the heat relay is called Pulse Width Modulation PWM For more information on PWM see Essay 000 Once the slab has reached the Melting temperature a timer starts The control remains in melting mode until the timer On Time reaches zero the Stop button is pushed or the remote switch is turned off Note If the remote switch is turned off and on ag...

Page 2: ...ssing or damaged please refer to the Limited Warranty and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance Type 650 includes One Snow Melting Control 650 One Slab Sensor 072 One Outdoor Sensor 070 One Data Brochure D 650 One Data Brochure D 001 Application Brochures A 650 Other information available Essay E 000 Essay E 600 Note ...

Page 3: ...Open Short Circuit The display flashes Err and the Slab Sensor pointer The control shuts down the melting system with this error Press and Release the Item button to change the display from the Outdoor temperature to the Slab Sensor temperature Use the arrow keys to program the Melting temperature Note The control automatically exits out of programming when the buttons are left alone for 20 second...

Page 4: ...4611 23rd Street Vernon B C Canada V1T 4K7 when agreed to by tekmar The installer or other qualified service person must at the owner s expense determine which component has failed The product must be returned complete with all of its components sensors base etc Products must be returned together with the proof of purchase to the original purchaser who then returns the product to tekmar after rece...

Reviews: