© 2015
532_D - 02/15
16 of 20
A Watts Water Technologies Company
Setting
Range
Default
SCHEDULE
The thermostat can follow a shared network schedule.
Select to follow either schedule master 1, 2, 3 or 4.
Requires tekmarNet.
1 to 4
1
The following additional settings are available when the thermostat is
unlocked
.
SET LIMIT ROOM MAX
Set the max room temperature limit while in the oc-
cupied time period. Available when a room sensor is
connected.
40 to 95°F
(4.5 to 35.0°C)
95°F
(35.0°C)
SET LIMIT ROOM MAX
Set the max room temperature limit while in the unoc-
cupied time period. Available when a room sensor is
connected and a schedule or scenes are selected.
40 to 95°F
(4.5 to 35.0°C)
95°F
(35.0°C)
SET LIMIT ROOM MIN
Set the min room temperature limit for both occupied and
unoccupied time periods. Available when a room sensor is
connected, and schedule or scenes are selected.
40 to 95°F
(4.5 to 35.0°C)
40°F
(4.5°C)
SET FLOOR MAX
Set the max floor temperature in order to protect the floor covering.
Available when an auxiliary floor sensor is connected. Suggested
settings: Tile = 90°F (32°C), Wood Floor = 85°F (29°C)
Off, 40 to 122°F
(Off, 4.5 to
50.0°C)
85°F
(29.5°C)
SENSOR 1
Select the type of sensor connected to auxiliary input 1.
Available when a sensor is automatically detected.
None, Room,
Flor, Out
Flor
SENSOR 2
Select the type of sensor connected to auxiliary input 2.
Available when a sensor is automatically detected.
None, Room,
Flor
Room
ROOM SENSOR
Select if the built-in room temperature sensor is on or
off. The built-in room sensor can only be disabled when
an auxiliary room or floor sensor is connected.
Off or On
On
AIR GROUP
Select if this thermostat should be included in an air
group to interlock heating and cooling for the group.
Requires tekmarNet.
Off, 1 to 16
Off
W PUMP
During a heat call, select whether or not the tN4 system
control's pump should turn on or be off to allow a zone group
pump per manifold. Requires a tekmarNet System Control.
Off or On
On
W DELAY
During a heat call, select whether or not the tN4 system
control's pump should be delayed by 3 minutes to
allow manifold thermal actuator zone valves to open.
Requires a tekmarNet System Control.
Off or On
Off
ESCAPE
Release the
and
buttons to return to the home screen.