background image

 

Important Warnings 
General 

 

Before using the device read this manual carefully. Keep it just in case of necessity. 

 

Abide all the rules and precautions stated in the manual. Follow all the instructions one by one. 

 

Keep the devices away from water and moisture 
 

 

Conditions 

Do not energize the device above or below the given limits of extreme hot or cold conditions, 

Temperature

Between

 -

10°C and +55°C

 

Relative Humidity: 

%95 RH max

 

 

Service 

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. 
 

In case of any defect or malfunction, contact with  your dealer or  with authorized service. All the technical 

interventions have to be done by technicians of company. 

 
 
 

 
 

Malfunctions that require technical service 

In case of any malfunction or below conditions contact with your authorized service,  

 

When Mains cable or the plug is harmed,  

 

Contact of device with a fluid,  

 

Exposure of rain and water,  

 

Fell down of device or harmed outer cover,  

 

Serious performance fall on the device,  

 

Depending on the instructions stated in manual, if your device not working properly 

Contact with your authorized service in such terms. 

 

Maintenance on your own  

Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any 
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have 

to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are 

allowed for cleaning 

 

Transportation 

Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions 

that caused by improper transportation is not under warranty.  

 

Human and Environmental Health

 

This device contains no chemical or biological elements that could harm human condition.  

 

 

 Technical Features

 

 

Power Input 

15V (min) 

 32V (max)  

Average Current Consumption (Normal Condition) 

180uA (@24V) 

Average Current Consumption (Alarm Condition) 

500uA (@24V)  

Operating Temperature Range 

-10

C ~ 55

C (14

F ~ 131

F) 

Humidity 

95% RH (max) 

Dimensions (mm) 

15,6mmx44,8mmx62,6mm 

Weight 

50gr(max) 

 
 

 
 

 

 

 
 

 
 

Setup 

Teknim  Analogue  Addressable  Input  /  Output  Modules  communicate  via  Flashlink  protocol.  The  device  is 
compatible with Analogue Addressable Panels (TFP-12XX series). The input / output connections of each model 

must be checked before terminal connections are made. Modules should also use 33K as the line end resistance 
and 10K as the alarm resistance. 

 

Addressing 

A special addressing module (TFCM-1801) designed by Teknim must be used to address the input and output 
modules. Modules can be addressed from 1 to 240. It should be noted that the addresses of each device in the 
vicinity must be unique. 

 
 

 
 

 
 

 
 

 

TFM-1220 

Analog

 

Addressable External Supply

  

Input/Output Module 

Installation & Operation Manual

 

Warning:

 Do not attempt to remove the electronic board from its plastic case. The electronic board is 

closed for your safety. Users should avoid from interference. 

 

Issue Date: 16/12/2019 

Rev:00 

Summary of Contents for TFM-1220

Page 1: ...satıcınız veya yetkili servisinizle irtibat kurunuz Cihaza teknik müdahale mutlaka kalifiye yetkili servis personeli tarafından yapılmalıdır Cihaz kuru bir bezle temizlenmelidir Herhangi bir kimyasal madde kullanılmamalıdır Taşıma ve Nakliye Cihaz dışarıdan herhangi bir darbeye maruz kalmayacak ve sıvı girişine mahal vermeyecek şekilde dikkatle taşınmalıdır Uygunsuz taşıma sırasında oluşan arızala...

Page 2: ...İ TEC 191018 bakınız Üretici Firma ve Merkez Servis AEEE yönetmeliğine uygundur Bu ürün geri dönüşümlü ve tekrar kullanılabilir nitelikteki yüksek kaliteli parça ve malzemelerden üretilmiştir Bu nedenle ürünü hizmet ömrünün sonunda evsel veya diğer atıklarla birlikte atmayın Elektrikli ve elektronik cihazların geri dönüşümü için bir toplama noktasına götürün 13 6 2014 tarihli ve 29029 sayılı Resmî...

Page 3: ... be done by technicians of company Device must be cleaned up with a dry fabric No chemicals are allowed for cleaning Transportation Device must be carefully transported avoiding all physical bump stroke and possible fluid entry Malfunctions that caused by improper transportation is not under warranty Human and Environmental Health This device contains no chemical or biological elements that could ...

Page 4: ...rm X It is constantly lit In case of output alarm X Blinks for 1s period Note When the blue led and the red led are lit at the same time a purple color appears 1922 Bilgi Elektronik San ve Tic A Ş Dudullu OSB 1 Cad İsmet Tarman İş Merkezi No 1 Kat 2 No 32 Ümraniye İstanbul 19 1922 CPR 1265 EN 54 18 2005 EN 54 18 2005 AC 2007 Input output device TFM 1200 Technical data see Doc BİLGİ TEC 191018 held...