TFP3304 

– TFP3308 Conventional Fire Alarm Panel 

                                       Issue Date: 07/08/2015 

FEATURES* 

 

Zone 

4 / 8 

Number of detector 
for each zone  

32 per zone ( Teknim  TFD series) 

EOL Resistors 

4,7k Ω 

Mains Supply 

230VAC  - %15 /  +%10              
Input 2A  fuse 

 

Internal PSU 

27,6 VDC SMPS 1,5A                   
with Automatic fuse 

AUX Power Output 

24 VDC 500mA with automatic fuse                                  

Siren Output 

2 Pcs 

24V DC, 500mA with automatic 
fuse 4,7k Ω EOL resistor 

Fire Relay 

30V 2A NC/NO dry contact 

Trouble Relay 

30V 2A NC/NO dry contact 

Battery 

2 Pcs 12V 7Ah ** 

 Battery voltage 

Min. 20 VDC.(Panel Shuts down 
below 20 VDC) 

Humidity 

95% RH (max) 

Temperature 

-10

C ~ 55

C (14

F ~ 131

F) 

Dimensions 

340 x 300 x 100 mm 

Weight 

4,4 kg ( without battery) 

 
*may be changed without notification. 
** Recommended battery with panel is Yuasa NP12-7 

***Max. Output current total 1A (Zones, AUX , Sirens)  

WARNINGS 

 

Warning:  Do  not  start  the  mounting  unless  read  this 
manual completely

 

 

 

Panel  includes  highly  sensitive  electronic  circuits. 
Because  of  that  reason,  don’t  start  to  use  unless  read 
this manual completely. 

 

In  case  of  any  failure  occur  or  need  to  maintain  of  the 
panel; all of these operations should be done authorized 
technical stuff only.  

 

All cabling should be done as indicated this manual. 

 

Do  not  attempt  to  change  wiring  while  system  under 
power tension. 

 

The panel must be earthed. 

 

NEVER  APPLY  230V  CITY  MAINS  NETWORK 
VOLTAGE  on  any  terminal  of  the  electronic  board

 

DEVICE FEATURES 

 

Supports 4 or 8 Zone. 

 

Has separate fire, trouble, off-line, test LEDs for 
each zone. 

 

Has General fault LED, System fault LED, siren 
status LED, PSU fault LED, ground fault LED, 
Battery fault LED, Power LED, On-Line LED, Test 
LED, Off-Line LED, Access level LED, 
Communication LED, General Alarm  

 

Smart battery charger, long battery life. While there 
is no main power, if battery supply voltage below 
than 20VAC, device automatically shuts down to 
protect batteries and prevent false alarm. 

 

EOL supervised siren output and zone inputs 

 

Zone test feature 

 

Auxiliary power output (AUX) 24 VDC 500mA with 
automatic fuse  

 

1 pc NC/NO fire relay (Button alarm, detector alarm 
etc.) 

 

1 pc NC/NO trouble relay (Power trouble, zone 
trouble, battery trouble etc.) 

 

Any zone can be bypassed, BYPASS led on the 
front panel, bypassed zones can be seen on LED 

 

 Key system to determine authorization level 

 

Easy to understand front panel,  

 

Switched power supply (

27,6 VDC SMPS 1,5A with 

automatic fuse)

 

 

Metal box 

 

Used with 2 pcs of 12V 7Ah battery.

 

 

Recommended battery with panel is Yuasa NP12-7

 

 

Summary of Contents for TFP3304

Page 1: ...ed technical stuff only All cabling should be done as indicated this manual Do not attempt to change wiring while system under power tension The panel must be earthed NEVER APPLY 230V CITY MAINS NETWORK VOLTAGE on any terminal of the electronic board DEVICE FEATURES Supports 4 or 8 Zone Has separate fire trouble off line test LEDs for each zone Has General fault LED System fault LED siren status L...

Page 2: ...back and top of the panel are available for easy mounting Firstly open the panel front cover by removing indicated screws Necessary key which take off the screws will provide with device Fix the panel on surface with provided screw apparatus by using four holes which is indicated by arrows Do not move mount of the panel from its place should be fixed steady POWER CONNECTION Make the electrical con...

Page 3: ...rn to its initial position of active relay fire condition must be ended and press on Reset button onto the panel Trouble Relay It changes contact and get active position during trouble warning and without power panel Trouble Relay returns to its initial position automatically as soon as trouble condition ends Power Output AUX There is 1 pc 24VDC 500mA lik mA power output with automatic fuse In cas...

Page 4: ...uses 2 pieces 12V 7AH batteries Zone Input Zone inputs supply to detector and button powers 24 V DC and provide to conduct signals such as fire short circuit and open circuit Each zone is capable of connecting up to 32 detectors and buttons Use 1x2x0 8 0 8JY st Y coded cable for connections between 0 500m Use 1x2x1 5 1 5J Y st Y coded cable for connections between 500 1500m Please make detectors a...

Page 5: ...e Button 6 Enter Button 7 Test mode Button 8 Reset Button 9 Keypad Lock 10 General Alarm Led 11 General Error Led 12 System Error Led 13 Siren Error Led 14 Supply Error Led 15 Earth Error Led 16 Battery Error Led 17 Energy Led 18 System On Led 19 Test Mode Led 20 Disable Mode Led 21 Access Level Led 22 Comm Mode Led ...

Page 6: ... error NO NO Supply error NO Indicates any supply error No supply Supply low or high voltage error Earth Error NO Indicates any earth error High voltage error Low voltage error Battery error NO Indicates any battery error No battery Low battery voltage Energy Indicates system powered by any supply NO NO NO System On Indicates device working properly NO NO NO Test Indicates one or more zone and sir...

Page 7: ... when test and disable turned off Turn on or turn off disable In this case disabled zones and sirens shown on the panel Enter NO Show details of errors During disable or test operation acknowledge or disacknowledge siren disable or test for the current zone NO Test Right direction Test buzzer and led Show zones and sirens in test for 3 seconds Change current zone or siren when disable is activated...

Page 8: ...hen Mains cable or the plug is harmed Contact of device with a fluid Exposure of rain and water Fell down of device or harmed outer cover Serious performance fall on the device Depending on the instructions stated in manual if your device not working properly further usage or possible wrong usage may cause other malfunctions Contact with your authorized service in such terms SPARE PART If the repa...