1
TFP3304
– TFP3308 Conventional Fire Alarm Panel
Issue Date: 07/08/2015
FEATURES*
Zone
4 / 8
Number of detector
for each zone
32 per zone ( Teknim TFD series)
EOL Resistors
4,7k Ω
Mains Supply
230VAC - %15 / +%10
Input 2A fuse
Internal PSU
27,6 VDC SMPS 1,5A
with Automatic fuse
AUX Power Output
24 VDC 500mA with automatic fuse
Siren Output
2 Pcs
24V DC, 500mA with automatic
fuse 4,7k Ω EOL resistor
Fire Relay
30V 2A NC/NO dry contact
Trouble Relay
30V 2A NC/NO dry contact
Battery
2 Pcs 12V 7Ah **
Battery voltage
Min. 20 VDC.(Panel Shuts down
below 20 VDC)
Humidity
95% RH (max)
Temperature
-10
C ~ 55
C (14
F ~ 131
F)
Dimensions
340 x 300 x 100 mm
Weight
4,4 kg ( without battery)
*may be changed without notification.
** Recommended battery with panel is Yuasa NP12-7
***Max. Output current total 1A (Zones, AUX , Sirens)
WARNINGS
Warning: Do not start the mounting unless read this
manual completely
Panel includes highly sensitive electronic circuits.
Because of that reason, don’t start to use unless read
this manual completely.
In case of any failure occur or need to maintain of the
panel; all of these operations should be done authorized
technical stuff only.
All cabling should be done as indicated this manual.
Do not attempt to change wiring while system under
power tension.
The panel must be earthed.
NEVER APPLY 230V CITY MAINS NETWORK
VOLTAGE on any terminal of the electronic board
DEVICE FEATURES
Supports 4 or 8 Zone.
Has separate fire, trouble, off-line, test LEDs for
each zone.
Has General fault LED, System fault LED, siren
status LED, PSU fault LED, ground fault LED,
Battery fault LED, Power LED, On-Line LED, Test
LED, Off-Line LED, Access level LED,
Communication LED, General Alarm
Smart battery charger, long battery life. While there
is no main power, if battery supply voltage below
than 20VAC, device automatically shuts down to
protect batteries and prevent false alarm.
EOL supervised siren output and zone inputs
Zone test feature
Auxiliary power output (AUX) 24 VDC 500mA with
automatic fuse
1 pc NC/NO fire relay (Button alarm, detector alarm
etc.)
1 pc NC/NO trouble relay (Power trouble, zone
trouble, battery trouble etc.)
Any zone can be bypassed, BYPASS led on the
front panel, bypassed zones can be seen on LED
Key system to determine authorization level
Easy to understand front panel,
Switched power supply (
27,6 VDC SMPS 1,5A with
automatic fuse)
Metal box
Used with 2 pcs of 12V 7Ah battery.
Recommended battery with panel is Yuasa NP12-7