5.
Do the wiring according to schematic shown below
.
TSD-701 NO
TSD-701 NC
6. Place the detector head back. Make sure the short line on head fits with long one on the base.
7. Energise the detector. If there is no alarm condition the LED on detector will be green color.
TEST
1.
After mounting of detector is done and it’s operating, gas exposed by a lighter to the convection window.
2. Detector turns to alarm mode in 30-40 seconds. It shut down the output and beeps continuously. Also LED
turns green to red.
3. Gas alarm density has been adjusted due to TS EN 50194-1 criteria. Detector stops alarm condition and turns
normal operating mode when gas density is decreased.
4. If the gas test is applied frequently, it shorten the life of detector reduces the sensitivity.
5. Detector that passed the test can be integrated to the system.
NOTES ON USING OF DETECTOR
TSD-701 series detectors must be used for detecting the type of gas which is written on it.
Average
life of the detector and sensor are 5 years. It’s recommended that all detectors be tested in every
year.
LED INFORMATION
Visual markings
Red LED
Gas Alarm
Yellow LED
Sensor Error
Green LED Continuous
Normal Operation
Green LED Flashing
Sensor Prepares
Audible Alerts
Continuous Beep
Gas Alarm
Cut Alert Sound
Sensor Error