background image

 

Astra-43A 

Addressable hardwired  

heat detector 

 

 

 

User guide 

Manufacturer: 
ZAO NTC TEKO 

420108, Russia, Kazan,  
Gafuri str., 71  
Tel.:+7(843) 528-03-69 

export@teko.biz 
www.teko.biz

 

 

Made in Russia 

 

 

Rev. 43

А-v1_7_instr_en 

  
 

 

1  FUNCTION 

The  detector  is  designed  for  detecting  fixed  tem-
perature  or  rate-of-rise,  forming  a 

‘fire  alarm’ 

notification  and  transferring the  notification to the 
Astra-A  RPA  via  Signaling  Line  Circuit  (SLC). 
Compatible  with  Control  Panels:  Astra

–812 Pro or 

Astra

–8945  Pro  (firmware  version  4_0  or  version 

higher).  

The detector provides measurement and transmission 
via  SLC  according  to  Astra-A  RPA  Extender  parame-
ter: 

ambient temperature (°С). 

    

● Astra–43A is powered by Astra-A RPA Extender. 

 

2  

SPECIFICATION

 

Power supply voltage, V ................................  7.5 

– 27.6 

Maximum current consumption, mA ......................... 0.5 
Response time, (sec.), at the rate of temperature rise 

°С/min ............................................................ 120–500 

10 

°С

/min ..........................................................60 - 242 

20 

°С

/min ..........................................................30 - 130 

30 

°С

/min ..........................................................20 - 100 

Response temperature, °С .................................54 - 65

 

Overall dimensions, mm: 
- diameter ................................................................. 106 
- height ........................................................................ 60

 

Operating Conditions 

Temperature range, 

°

С

 ....................... from - 30 to + 70 

Relative air humidity

, % ...................... up to 93 at +40

°

С 

 

without moisture condensation

 

3  DELIVERY  SET 

Delivery set includes: 

fastening parts (dowels 

– 2 pcs., 

screws 

– 2 pcs.), 

user guide 

– 1 pc

 
 

 
 
 
 

4  INDICATION

 

Status

 

Red LED 

Standby mode 

1-time  flash  with  a  period  of  8-9 
sec. 

Fire alarm 

1 time flash with a period of 2 sec. 
when  the  response  temperature  is 
reached 

Fire test 

1-time flash with a period of 2 sec. 
within  30  sec.  after  receiving  the 
"Test"  command  from  the  Laser 
Pointer "Astra-942" (LP) 

Detector's 
failure 

3 times flashes with a period of 25 
sec. until the failure is fixed 

Command 
receiving 
(LaserPointer) 

1 time flash for 2-5 sec 

 

5  ADDING TO THE SYSTEM 

1) 

Connect  the  RPA  to  the  Control  Panel  using  RS-

485 interface.  

2) 

Add the Astra-A RPA Extender to the Control 

Panel according to the 

user guide of the panel

 Astra-812 

Pro or the PKM Astra Pro built-in manual. 

3) 

 Remove the electronic unit 

by  turning  it  counterclockwise 
relative to the base. 

4) 

Connect  the  SLC  power 

(terminals  "+"  and  "-")  and  the 
SLC  interface  (terminals  "A" 
and  "B")  from  the  Astra-A  RPA 
to the terminals on the base. 

5) 

Run  the  RPA  registration 

mode  according  to  the 

user 

guide  of  the  panel

.  It  takes 

60 sec to register a detector.  

6) 

Run the registration mode 

via two possible ways: 
- setting the detector on the base (p. 8, a. 5

)

 (power is 

on and SLC connected); 

Reviews: